Delta Electronics AC Drive VFD-F Series User Manual page 125

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
Group 6 Protection Function Parameters (Twice the value for 460V class)
Parameters
06-00
Over-voltage Stall Prevention 230V: 330.0~410.0VDC
06-01
Over-current Stall Prevention
during Acceleration
06-02
Over-current Stall Prevention
during operation
06-03
Over-torque Detection
Selection
06-04
Over-torque Detection Level 30~150%
06-05
Over-torque Detection Time 0.1~60.0 Sec
06-06
Electronic Thermal Relay
Selection
06-07
Electronic Thermal
Characteristic
06-08
Low Current Detection Level 00~100% (00 disabled)
06-09
Low Current Detection Time 0.1~ 3600.0 Sec
06-10
Low Current Detection
Treatment
06-11
Present Fault Record
06-12
Second Most Recent Fault
Record
06-13
Third Most Recent Fault
Record
Functions
Settings
460V: 660.0~820.0VDC
00: Disable
20~150%
00: Disable
20~150%
00: Disable
00: Over-torque detection
disabled.
01: Over-torque detection enabled
during constant speed
operation (OL2), and operation
continues.
02: Over-torque detection enabled
during constant speed
operation (OL2), and operation
halted.
03: Over-torque detection enabled
during operation (OL2), and
operation continues.
04: Over-torque detection enabled
during operation (OL2), and
operation halted.
00: Operate disabled.
01: Operate with a standard motor.
02: Operate with a special motor.
30~600 Sec
00: Warn and ramp to stop
01: Warn and coast to stop
02: Warn and keep operating
00: No fault
01: Oc (over-current)
02: Ov (over-voltage)
03: OH (over temperature)
04: OL (over load)
8-12
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory
Customer
Setting
390.0
780.0
120
120
00
110
0.1
02
60
00
10.0
01
00
00
00