VFD-F Series
Fault
Fault Descriptions
Name
The AC drive
temperature sensor
detects excessive heat.
The AC drive detects
that the DC bus voltage
has fallen below its
minimum value.
The AC drive detects
excessive drive output
current.
Note: The AC drive can
withstand up to 150% of
the rated current for a
maximum of 60
seconds.
Internal electronic
overload trip
Motor overload. Check
the parameter settings
(Pr.6-03 to Pr.6-05)
GFF hardware error
CC (Current Clamp)
Corrective Actions
1. Ensure that the ambient temperature
falls within the specified temperature
range.
2. Make sure that the ventilation holes are
not obstructed.
3. Remove any foreign objects on the
heatsinks and check for possible dirty
heat sink fins.
4. Provide enough spacing for adequate
ventilation.
Check whether the input voltage falls within
the rated AC drive's input voltage.
1. Check whether the motor is overloaded.
2. Reduce torque compensation setting as
set in Pr.7-02.
3. Increase the AC drive's output capacity.
1. Check for possible motor overload.
2. Check electronic thermal overload
setting.
3. Increase motor capacity.
4. Reduce the current level so that the drive
output current does not exceed the value
set by the Motor Rated Current Pr.7-00.
1. Reduce the motor load.
2. Adjust the over-torque detection setting
to an appropriate setting (Pr.06-03 to
Pr.06-05).
Return to the factory.
Return to the factory.