Carrier 48/50PD05 User Manual page 102

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

ITEM
EXPANSION
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
N.HTR
Number of Heat Stages
MRT.H
Heat Minimum On Time
MOT.H
Heat Minimum Off Time
H.DEC
Heat Stage Decrease
Time
H.INC
Heat Stage Increase Time
FOD.E
Fan--- off Delay, Elect Heat
FOD.G
Fan--- off Delay, Gas Heat
HT.LO
Heating Lockout Temp
SAT
SUPPLY AIR
TEMPERATURE
SAT.H
SAT Heat Mode Sensing
SAM.L
Maximum SAT Lower
Level
SAM.U
Maximum SAT Upper
Level
SPT
SPACE TEMPERATURE
HT.PD
SPT Heat Demand (+)
Level
HT.ND
SPT Heat Demand (--- )
Level
H.LAG
Heat Thermal Lag Factor
ECON
Economizer Configuration
EC.EN
Economizer Installed
E.CTL
Economizer Control Type
MP .25
Econ Min at 25%
Fanspeed
MP .50
Econ Min at 50%
Fanspeed
MP .75
Econ Min at 75%
Fanspeed
MP .MX
Econ Min at Max
Fanspeed
EC.MX
Econo Cool Max Position
M.ANG
Min Actuator Ctrl Angle
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
DF.DB
Diff Dry Bulb Control
UEFC
Unoccupied Free Cooling
FC.TM
Free Cool PreOcc Time
FC.LO
Free Cool Low Temp Limit
PE.EN
Power Exhaust Installed
PE1.C
Power Exhaust Stage1
CFM
PE2.C
Power Exhaust Stage2
CFM
IDF.C
Indoor Fan Max Speed
CFM
EN.SW
Enthalpy Switch
Table 65 — MODE - CONFIGURATION (cont)
RANGE
UNITS
0=No Heat
1=Gas
2=Electric
1 to 2
60 to 999
sec
60 to 999
sec
120 to 999
sec
120 to 999
sec
10 to 600
sec
45 to 600
sec
40 to 125F
dF
Enable/Disable
85 to 200
dF
85 to 200
dF
0.5 to 5
^F
--- 5 to --- 0.5
^F
0 to 5
min
Yes/No
1=Dig/Position
2=Dig/Command
3=Analog Ctrl
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
75 to 90
40 to 100F
dF
--- 30 to 50F
dF
Disable/Enable
0=Disabled
1=Unoccupied
2=Preoccupancy
1 to 9999
min
--- 30 to 70F
dF
Yes/No
100 to 15000
cfm
100 to 15000
cfm
500 to 15000
cfm
0=No Switch
1=Normal Open
2=Normal Closed
102
CCN
DEFAULT
TABLE/SUB--- TABLE
HEAT_CFG
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with
electric heat)
1 (50 series <15kW)
2 (48 series, 50
series >=15kW)
120
120
300
450
30
45
75
Disable
140
160
1
--- 1
1
ECON_CFG
No: no FIOP
Yes: FIOP
1
0
0
0
30
100
88
65
0
Enable
2
120
50
No: no FIOP
Yes: FIOP
600
0
1600 (05)
2000 (06)
0: no FIOP
1: FIOP
CCN POINT
ENTRY
HEATTYPE
NUM_HEAT
HMIN_ON
HMIN_OFF
HSTAGDEC
HSTAGINC
ELEC_FOD
GAS_FOD
OATLHEAT
SAT_HEAT
SATMAX_L
SATMAX_H
HDEM_POS
HDEM_NEG
HEAT_LAG
ECONO
ECON_CTL
MINP_25
MINP_50
MINP_75
MINP_MAX
ECONOMAX
MINANGLE
OATLECLH
OATLECLL
DIFFBULB
UEFC_CFG
UEFCTIME
OATLUEFC
PE_ENABL
PE1_CFM
PE2_CFM
IDF_CFM
ENTHLCFG