Carrier 48/50PD05 User Manual page 19

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

For all units with Economizers:
1. 1.The outdoor temperature is below the Econo Cool Hi
Temp Limit (Configuration→ECON→EH.LO) and above
the
Econo
Cool
(Configuration→ECON→EL.LO).
For units with Enthalpy Control
2. 1.The outdoor enthalpy is low and the outdoor temperature
is
below
the
Econo
(Configuration→ECON→EH.LO) and above the Econo
Cool Lo Temp Limit (Configuration→ECON→EL.LO).
If the conditions above are true and the economizer is available for
cooling the economizer outside air and return air dampers will
modulate to allow proportions of outside air and return air to mix
and produce a temperature equal to the Cool Supply Air Set Point
(Setpoint→SASP).
If reset is applied to the Supply Air
Temperature Set Point (Setpoint→SASP) the dampers will control
to the Supply Air Control Point (Run Status→COOL→SA.CP).
If the conditions above are true but the economizer dampers are not
able to satisfy the Cool Supply Air Set Point (Setpoint→SASP)
with Reset (if applied), the compressor will turn on and modulate
to provide additional cooling to satisfy the Cool Supply Air Set
Point (Setpoint→SASP) with Reset if applied.
If the conditions above are not true, the economizer will move to a
user
Configurable
Econ
(Configuration→ECON→MP.MX)
economizer damper position is based on the Supply Fan Maximum
Speed (Configuration→UNIT→FS.MX).
maintain a constant airflow through the economizer by opening the
dampers more as the indoor fan speed is reduced or closing the
dampers more as the indoor fan speed increases.
The shape of the Economizer Minimum Position vs. Fan Speed
curve is determined by the configuration parameters: Econ Min at
25% Fan speed (Configuration→ECON→MP.25), Econ Min at
50% Fan speed (Configuration→ECON→MP.50), Econ Min at
75% Fan speed (Configuration→ECON→MP.75) and Econ Min
at Max Fan speed (Configuration→ECON→MP.MX).
The
Econ
Min
(Configuration→ECON→MP.25), Econ Min at 50% Fan speed
(Configuration→ECON→MP.50) and Econ Min at 75% Fan
speed (Configuration→ECON→MP.75) damper positions are
calculated based on the Econ Min at Max Fan Speed
(Configuration→ECON→MP.MX) and Supply Fan Maximum
Speed (Configuration→UNIT→FS.MX).
The
Econ
Min
(Configuration→ECON→MP.25), Econ Min at 50% Fan speed
(Configuration→ECON→MP.50) and Econ Min at 75% Fan
speed (Configuration→ECON→MP.75) damper position are user
configurable and can be determined by setting the fan speed at 25,
50 and 75% and determining the damper position required to
maintain
the
Econ
Min
(Configuration→ECON→MP.MX) Outside air CFM through the
economizer outside air dampers.
programmed into the PD controls is based on a side shot
economizer at 400 CFM/TON Supply Air flow with negative 0.25
in H
O pressure in the return duct.
2
Econ Min at Max fan Speed (Configuration→UNIT→FS.MN) is
set by user based on minimum required outside air ventilation
CFM required for the application. This procedure would be the
same as if this were a CV unit with the unit running at the design
point CFM. This determines the minimum position amount of
outside air CFM required when the fan is running at maximum
speed.
Configure
the
Indoor
(Configuration→ECON→IDF.C) either to the supply CFM
determined from the fan performance tables or air balance reports.
If using fan performance tables make corrections for all installed
accessory pressure loss and use measured RPM, power and static
Lo
Temp
Limit
Cool
Hi
Temp
Limit
Min
at
Max
Fan
Speed
where
the
minimum
This is done to
at
25%
Fan
speed
at
25%
Fan
speed
at
Max
Fan
Speed
The default calculations
Fan
Max
Speed
CFM
pressure readings to determine the actual Indoor Fan Max Speed
CFM (Configuration→ECON→IDF.C).
ECON MIN
AT MAX
FANSPEED
POSITION
(MINP_MAX)
VENTILATION FOR PEOPLE
MINIMUM
IAQ
DAMPER
POSITION
VENTILATION FOR SOURCES
(AQ. MN)
100
AQ
DIFFERENTIAL
LOW (AQD.L)
Fig. 8 - - Economizer Minimum Position
If the indoor fan is not operating, the economizer will be fully
closed, 0% open.
Ventilation Mode
If the space temperature falls 0.5F below the Occupied Cool Set
Point (Setpoints→OCSP) the compressor will turn off, the indoor
fan speed will be set to the Vent Mode Fan Speed
(Configuration→UNIT→FS.VM) and the economizer will open
to the position that will supply minimum ventilation air at the
configured
Vent
(Configuration→UNIT→FS.VM). Default Vent Mode Fan Speed
(Configuration→UNIT→FS.VM) is 50%. Configuring the Vent
Mode Fan Speed (Configuration→UNIT→FS.VM) lower will
provide additional energy savings in vent mode but may not
supply the required ventilation air to the conditioned space at lower
fan speeds.
Demand Control Ventilation
The 48PD units can also be equipped with optional CO
for additional indoor air quality control. When unit is equipped
with a return duct CO
sensor or return duct CO
2
outside air CO
sensor the Economizer minimum position vs. fan
2
speed curve will be recalculated based on the CO
return and/or outside air as shown in Fig. 8. See the Indoor Air
19
700
INSIDE/OUTSIDE CO
DIFFERENTIAL
AQ
DIFFERENTIAL
HIGH (AQD.H)
C09145
Mode
Fan
Speed
sensors
2
sensor and
2
level of the
2
2