AIRFLOW
0.2
(Cfm)
Rpm
1200
422
1300
439
1400
457
1500
477
1600
498
1700
521
1800
545
1900
569
2000
595
AIRFLOW
1.2
(Cfm)
Rpm
1200
911
1300
913
1400
918
1500
925
1600
934
1700
944
1800
956
1900
970
2000
985
LEGEND
Bhp - - Brake Horsepower
__
High Range Motor/Drive Required
AIRFLOW
0.2
(Cfm)
Rpm
1500
491
1600
513
1700
537
1800
561
1900
586
2000
613
2100
640
2200
667
2300
695
2400
724
2500
753
AIRFLOW
1.2
(Cfm)
Rpm
1500
932
1600
942
1700
953
1800
966
1900
980
2000
996
2100
1012
2200
1030
2300
1049
2400
1068
2500
1089
LEGEND
Bhp - - Brake Horsepower
Low Range Motor/Drive Required
Table 58 — Fan Performance - 50PD05 Horizontal Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Bhp
Rpm
Bhp
0.11
548
0.19
0.13
561
0.21
0.16
577
0.24
0.19
593
0.27
0.22
611
0.31
0.25
630
0.35
0.29
650
0.40
0.34
672
0.45
0.39
694
0.51
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Bhp
Rpm
Bhp
0.53
986
0.63
0.57
986
0.68
0.62
989
0.72
0.67
995
0.78
0.72
1002
0.84
0.78
1010
0.90
0.85
1021
0.97
0.92
1033
1.04
1.00
1047
1.13
Table 59 — Fan Performance - - 50PD06 Horizontal Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
Bhp
Rpm
Bhp
0.19
604
0.28
0.23
623
0.32
0.27
643
0.37
0.31
664
0.42
0.36
686
0.47
0.41
709
0.53
0.47
732
0.60
0.54
757
0.67
0.61
782
0.75
0.69
807
0.84
0.78
833
0.93
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
Bhp
Rpm
Bhp
0.68
1002
0.79
0.73
1009
0.85
0.80
1019
0.91
0.86
1030
0.99
0.94
1043
1.06
1.02
1057
1.15
1.11
1072
1.24
1.20
1088
1.34
1.30
1106
1.44
1.41
1124
1.56
1.53
1143
1.68
0.6
0.8
Rpm
Bhp
Rpm
652
0.26
745
662
0.29
752
674
0.33
761
688
0.37
773
704
0.41
786
720
0.46
801
738
0.51
817
757
0.57
834
777
0.63
852
1.6
1.8
Rpm
Bhp
Rpm
1056
0.74
1123
1056
0.78
1122
1058
0.84
1123
1061
0.89
1125
1067
0.95
1129
1074
1.02
1135
1083
1.09
1143
1094
1.17
1152
1106
1.26
1162
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
0.6
0.8
Rpm
Bhp
Rpm
697
0.37
781
714
0.42
795
731
0.47
810
750
0.52
827
770
0.58
845
790
0.65
864
812
0.72
884
834
0.80
904
857
0.89
926
881
0.98
948
905
1.08
971
1.6
1.8
Rpm
Bhp
Rpm
1068
0.91
1132
1074
0.97
1136
1082
1.04
1143
1092
1.11
1151
1103
1.19
1161
1115
1.28
1172
1129
1.38
1184
1144
1.48
1198
1160
1.59
1213
1178
1.71
1229
1196
1.84
1246
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
98
1.0
Bhp
Rpm
Bhp
0.35
831
0.44
0.38
835
0.47
0.42
842
0.51
0.46
851
0.56
0.51
862
0.61
0.56
875
0.67
0.62
889
0.73
0.68
904
0.80
0.75
921
0.87
2.0
Bhp
Rpm
Bhp
0.85
1187
0.96
0.90
1185
1.01
0.95
1185
1.07
1.01
1186
1.14
1.08
1189
1.21
1.15
1194
1.28
1.23
1200
1.36
1.31
1208
1.45
1.40
1217
1.54
1.0
Bhp
Rpm
Bhp
0.47
859
0.57
0.52
871
0.62
0.57
884
0.68
0.63
899
0.75
0.70
915
0.82
0.77
932
0.89
0.85
950
0.97
0.93
969
1.06
1.02
989
1.16
1.12
1010
1.26
1.23
1032
1.38
2.0
Bhp
Rpm
Bhp
1.03
1192
1.15
1.09
1196
1.22
1.17
1201
1.30
1.24
1208
1.38
1.33
1217
1.47
1.42
1227
1.56
1.52
1238
1.67
1.63
1251
1.78
1.74
1265
1.89
1.86
1279
2.02
1.99
1295
2.16

Hide quick links: