ITEM
EXPANSION
AIR.Q
Air Quality Config.
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Config
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
O.20M
OAQ Sensor Value at
20mA
H.4M
RH Sensor Value at 4mA
H.20M
RH Sensor Value at 20mA
ALM.O
Alarm Relay Config.
A.SPC
SPT/SPRH Sensor Failure
A.SRT
SAT/RAT Sensor Failure
A.OAT
OAT Thermistor Failure
A.CS
Current Sensor Failure
A.CMP
Compressor Failure
A.CKT
Refrig Circuit Failure
A.SSP
SSP Transducer Failure
A.SCT
SCT Thermistor Failure
A.FAN
Indoor Fan Failure
A.FIL
Dirty Filter
A.ECO
Economizer Failure
PID
PID Configurations
EC.P
Economizer PID --- kP
EC.I
Economizer PID --- kI
EC.D
Economizer PID --- kD
EC.DT
Economizer PID --- rate
E.DBD
Economizer PID
Deadband
CP .P
Capacity PID --- kP
CP .I
Capacity PID --- kI
CP .D
Capacity PID --- kD
CP .DT
Capacity PID --- rate
LK.P
Linkage Staging PID --- kP
LK.I
Linkage Staging PID --- kI
LK.D
Linkage Staging PID --- kD
LK.DT
Linkage Staging PID ---
rate
Table 65 — MODE - CONFIGURATION (cont)
RANGE
UNITS
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0=Never
1=Occupied
2=Always
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0=Never
1=Occupied
2=Always
0 to 100
%
0 to 100
%
0=No OAQ
1=DCV
2=Lockout OAQ
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 50
%
60 to 100
%
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
0.0 to 99.9
0.0 to 99.9
0.0 to 99.9
10.0 to 180.0
sec
0 to 25
%
0 to 99.9
0 to 99.9
0 to 99.9
1 to 30
secs
0.0 to 99.9
0.0 to 99.9
0.0 to 99.9
10.0 to 180.0
secs
103
CCN
DEFAULT
TABLE/SUB--- TABLE
IAQ_CFG
0: no FIOP
1: FIOP
0
0
0
10
100
0
600
100
700
600
200
0
2000
0
2000
0
100
ALM_CFG
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
PID_CFG
2.5
0.1
1
15
3
1.5
0.1
1
5
10
5
5
30
CCN POINT
ENTRY
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
IAQMINP
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ_LOW
DAQ_HIGH
DAQFNON
DAQFNOFF
IAQ_4MA
IAQ_20MA
OAQ_4MA
OAQ_20MA
RH_4MA
RH_20MA
SPACE_AL
SATRATAL
OAT_AL
CS_AL
COMP_AL
CKT_AL
SSP_AL
SCT_AL
FAN_AL
FILT_AL
ECON_AL
ECONO_P
ECONO_I
ECONO_D
ECONO_DT
ECONBAND
VCAP_P
VCAP_I
VCAP_D
VCAP_DT
LINK_P
LINK_I
LINK_D
LINK_DT