ALARM
ALARM NAME
CODE
IN PANEL
2001
---
2002
---
2003
---
2004
DIR LOCK
2005
I/O COMM
2006
Al1 LOSS
2007
Al2 LOSS
2008
PANEL LOSS
2009
---
2010
MOT OVERTEMP
2011
UNDERLOAD
2012
MOTOR STALL
2013*
AUTORESET
2014
AUTOCHANGE
2015
PFA INTERLOCK
2016
---
2017*
OFF BUTTON
2018
PID SLEEP
2019
ID RUN
2020
OVERRIDE
START ENABLE 1
2021
MISSING
START ENABLE 2
2022
MISSING
2023
EMERGENCY STOP
* This alarm is not indicated by a relay output, even when the relay output is configured to indicate alarm conditions, parameter 1401 RELAY OUTPUT = 5 (ALARM) or 16
(FLT/ALARM).
Table 43 — MAINTENANCE INTERVALS
MAINTENANCE
Heat sink temperature check and
cleaning
Main cooling fan replacement
HVAC Control panel battery change
APPENDIX B - VFD INFORMATION (CONT)
Table 42 — ALARM CODES
DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
Reserved
Reserved
Reserved
The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or
Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT
TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on
line.
Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the
parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001).
Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check
parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001).
Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the
VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the
control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and
parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).
Reserved
Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload
fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009).
Check the temperature sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the
motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to
3015.
Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To
control automatic reset, use parameter group 31 (AUTOMATIC RESET).
This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the
Pump Alternation macro.
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when
Autochange is used), or a speed regulated motor (when Autochange is not used).
Reserved
This alarm indicates that the OFF button has been pressed.
This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID
sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126.
The VFD is performing an ID run.
Override mode is activated.
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To
correct, check the digital input configuration and the communication settings.
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter1609. To
correct, check the digital input configuration and the communication settings.
Emergency stop is activated.
INTERVAL
Every 6 to 12 months (depending
on the dustiness of the
environment)
Every five years
Every ten years
89