Carrier 48/50PD05 User Manual page 71

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
ITEM
EXPANSION
SETPOINTS
OCSP
Occupied Cool Setpoint
UCSP
Unoccupied Cool Setpoint
OHSP
Occupied Heat Setpoint
UHSP
Unoccupied Heat Setpoint
GAP
Heat--- Cool Setpoint Gap
STO.R
SPT Offset Range (+/--- )
SASP
Cool Supply Air Setpoint
RH.SP
Space RH Setpoint
RH.DB
Space RH Deadband
C.LO
Compressor Lockout Temp
HT.LO
Heating Lockout Temp
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
FC.LO
Free Cool Low Temp Limit
ITEM
EXPANSION
INPUTS
GEN.I
General Inputs
FIL.S
Filter Status Switch
FAN.S
Fan Status Switch
FDWN
Fire Shutdown Switch
ENTH
Outdoor Enthalpy Switch
RM.OC
Remote Occupancy Switch
HUM
Space Humidity Switch
CMP .A
Compressor A Feedback
C.ALM
Scroll Compressor Alarm
CS.IN
Current Sensor Inputs
CS.A1
Compressor A1 Feedback
AIR.Q
Air Quality Inputs
IAQ.S
IAQ Level (switch)
IAQ
IAQ Level (sensor)
OAQ
OAQ Level (sensor)
SP .RH
Space Humidity Sensor
Table 31 — MODE - SET POINTS
RANGE
UNITS
DEFAULT
55 to 80F
dF
78
75 to 95F
dF
85
55 to 80F
dF
68
40 to 80F
dF
60
2 to 10F
^F
5
0 to 5F
^F
5
45 to 75
dF
65
30 to 95
%
50
2 to 20
%
5
0 to 100F
dF
0
40 to 125F
dF
75
40 to 100F
dF
65
--- 30 to 50F
dF
0
0 to 70F
dF
50
Table 32 — MODE - - INPUTS
RANGE
UNITS
CCN TABLE/SUB--- TABLE
STATUS DISPLAY
UINPUTS
Dirty/Clean
On/Off
On/Off
High/Low
On/Off
High/Low
On/Off
On/Off
On/Off
High/Low
xxxx
ppm
xxxx
ppm
xxx.x
%
71
CCN TABLE/SUB--- TABLE
SETPOINT CONFIGURATION
SET_PNT
CCN
POINT
STATUS
FILTSTAT
forcible
FAN_STAT
forcible
FIREDOWN
forcible
ENTHALPY
forcible
REM_OCC
forcible
HUM_STAT
forcible
COMP_A
COMP_ALM
CS_A1
IAQIN
forcible
IAQ
forcible
OAQ
forcible
SPRH
forcible
CCN POINT
OCSP
UCSP
OHSP
UHSP
HCSP_GAP
SPTO_RNG
SASP
SPRH_SP
SPRH_DB
OATLCOMP
OATLHEAT
OATLECLH
OATLECLL
OATLUEFC
CCN
DISPLAY
WRITE
WRITE
STATUS
forcible
forcible
forcible
forcible

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0548pd0650pd0550pd06

Table of Contents