Cooling Test

The cooling (COOL) submenu is used to change output status for
testing the cooling function. The fans (FANS) and heating (HEAT)
service test outputs are reset to OFF for the cooling service test.
The digital scroll controller power test (CTLR) turns on and off the
compressor controller. The compressor capacity test (CPAC) is
used to run the compressor at a desired capacity of 15% to 100%.
If a capacity is chosen between 1 and 14, the capacity will be set to
15%.
The outdoor fan will turn on to high speed when the
compressor capacity is 15% or greater. The indoor fan speed will
default to supply fan maximum speed (FS.MX) when the
compressor capacity test is first activated. The cool test fan speed
(F.SPD) is used to change the fan speed while the compressor is
running. All normal cooling alarms and alerts are functional.
IMPORTANT: When charging the unit, both the compressor
capacity test and the cool test fan speed should be set to 100%.

Heating Test

The heating (HEAT) submenu is used to change output status for
the individual heat stages, gas or electric. The fans (FANS) and
cooling (COOL) service test outputs are reset to OFF for the
heating service test. Indoor and outdoor fans are controlled
normally to maintain proper unit operation. The indoor fan speed
will run at the configured max speed FS.MX. All normal heating
alarms and alerts are functional.
Table 5 — Service Test Modes and Submodes Directory
DISPLAY MENU/
SUB- -MENU/
EXPANDED NAME
NAME
SERVICE TEST
Field Service Test Mode
TEST
INDP
Test Independent Outputs
ECON
Economizer Position Test
E.CAL
Calibrate Economizer
PE.1
Power Exhaust 1 Test
PE.2
Power Exhaust 2 Test
ALRM
Alarm Relay Test
CCH
Crankcase Heat Test
FANS SUPPLY
Test Fans
IDF
VFD Power Test
F.SPD
Indoor Fan Speed Test
OFC.1
Outdoor Fan Relay Test
COOL
Test Cooling
CTLR
Dig Scroll Ctrl Pwr Test
CAPC
Compressor Capacity Test
F.SPD
Cool Test Fan Speed
HEAT
Test Heating
HT.1
Heat Stage 1 Test
HT.2
Heat Stage 2 Test

THIRD PARTY CONTROL

Third party controls may interface with the unit ComfortLinkt
controls through the connections described below. See other
sections of these instructions for more information on the related
unit control and configurations.

Remote Occupancy

The remote occupancy input is provided on the field connection
terminal
board
(TB1).
The
configuration, Configuration→UNIT→RM.SW, identifies the
normally open or normally closed status of this input when
unoccupied.
S 5 = 24 VAC signal input
S 6 = 24 VAC source for dry contact
VALUES
On/Off
0 to 100%
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0 to 100%
On/Off
On/Off
0 to 100%
0 to 100%
On/Off
On/Off
Remote
Occupancy
Switch

Fire Shutdown

The fire shutdown input is provided for unit shutdown in response
to a fire alarm or smoke detector. The Fire Shutdown Switch
configuration, Configuration→UNIT→FS.SW, identifies the
normally open or normally closed status of this input when there is
no fire alarm.
Input at field connection terminal board (TB1)
S Fire Shutdown 1 = 24 VAC source for dry contact
S Fire Shutdown 2 = 24 VAC signal input

Alarm Output

The alarm output is provided on the field connection terminal
board (TB1) to indicate a current alarm status. The output will be
24VAC if a current alarm exists.
S C = 24 VAC common
S X = 24 VAC signal output

Economizer Monitoring

On field terminal board (TB1), terminals 8, 9, and 10 can be used
to monitor economizer position from a third party control system.
See economizer operation section for additional information.
In digital mode (E.CTL = 1 or 2), the economizer commanded
position can be read as a 2- -10v or 4- -20mA signal. TB1- -8 and
TB1- -9 are used as follows:
S To read a 2- -10v signal, disconnect the violet wire on
TB1- -J10- -8 and place volt meter device across TB1- -8 and
TB1- -9.
S To read a 4- -20mA signal, disconnect the violet wire on
TB1- -J10- -8 and the 500Ω resister at TB1- -J10- -6. Place amp
meter device between TB1- -8 and TB1- -9.
In analog mode (E.CTL = 3), the economizer position can be read
as a 2- -10v feedback signal across TB1- -10 and TB1- -9 at any time.
IMPORTANT:
The violet wire and 500Ω resister must be
connected at the J10 connector as originally wired to operate the
economizer in analog mode.

Economizer Damper Control

For units with the economizer option or accessory and the ECB
control board, the damper position can be directly controlled
through the IAQ sensor input provided on the field connection
terminal
board.
The
IAQ
Configuration→AIR.Q→IA.CF will have to set to 3 (Control
Minimum Position). When IA.CF = 3, an external 4 to 20 mA
source is used to move the damper 0% to 100% directly.
Terminal 2 = 4- -20mA + signal
Terminal 3 = 4- -20mA - - common
IMPORTANT:
In this mode preset minimum positions
configurations are not valid. The damper position may exceed the
input position to provide economizer cooling and CO
can not be used for DCV control. Refer to the Indoor Air Quality
operation section for more information.

CONTROLS OPERATION

Display Configuration

The Configuration→DISP submenu is used to configure the local
display settings.
Metric Display (METR)
This variable is used to change the display from English units to
Metric units.
Language Selection (LANG)
This variable is used to change the language of the ComfortLink
display. At this time, only English is available.
11