Appendix
Standard values for burner adjustment
Note
Check that the service instructions are valid for the relevant burner (see notes
on applicability, page 52 and serial no. on the burner type plate).
In conjunction with Vitoplex 100 and 300
Nozzle pressure table and mixing assembly settings
Gas
Wobbe index
group
Wo
3
kWh/m
Nat.
15.00
gas E
Nat.
12.40
gas LL
Std . values for mixing assembly settings
1 mbar equals nearly 10 mmWS; e.g. 12.0 mbar [ 120 mmWS.
*1
The nozzle pressures apply to 15 ºC, 1013 mbar, dry.
Gas throughput subject to the net calorific value during operation (H
Gas
Net calorific
group
value during op.
H
H
uB
3
kWh/m
Nat.
9.45
gas E
Nat.
8.13
gas LL
Note
Partial load gas throughput equals 60 % of the full load gas throughput.
44
Supply
p
press.
3
*1
MJ/m
mbar
54.00
20.0
44.60
20.0
g p
3
MJ/m
34.02
Gas
throughput
29.25
Gas
throughput
Rated boiler output
Nozzle
Stg. 1
press.
Stg. 2
*1
mbar
Nozzle
Stg. 1
press.
Stg. 2
10.8
*1
mbar
mm
Rated boiler output
kW
kW
3
m
/h
litres/min
153
3
m
/h
10.7
litres/min
178
80
105
130
kW
kW
kW
kW
kW
kW
3.7
4.2
2.4
9.0
10.0
5.9
4.4
5.2
2.6
12.6
6.8
8.0 14.0 15.0 19.0 22.0
80
105
130
kW
kW
kW
kW
9.2
12.1
15.0
19.6
201
250
14.0
17.4
22.7
234
289
170
225
kW kW
kW
kW
2.9
3.7
7.6
8.9
3.5
4.9
9.4
11.5
)
uB
170
225
kW
kW
kW
kW
25.9
326
431
30.1
379
501