Initial start−up, inspection and maintenance
Further details regarding the individual steps
Checking the static and the supply pressure
Check the gas type with your local gas supplier.
The burner is factory−adjusted for natural gas E.
Adjust the nozzle pressure for operation with natural gas LL according to the
table on pages 44 to 46.
Record the gas type in the service report (see from page 47).
10
(cont.)
Static pressure
1. Close the gas shut−off valve.
2. Release the screw in test port A,
but do not remove.
3. Connect the U−shaped pressure
gauge.
4. Open the gas shut−off valve.
5. Measure the static pressure (max.
50 mbar).
6. Record the actual values in the
service report (see from page 47).