Burner Control Unit - Viessmann Vitoflame 100 Service Instructions Manual

Pressure−jet gas burner. for vitoplex 100, 200 and 300. rated output 80 to 225 kw. for vitorond 200. rated output 125 to 195 kw
Table of Contents

Advertisement

Burner control unit

Program sequence during commissioning
A
Start command
B B'
Interval before the flame has
built
C
Burner operating position
reached
C D
Burner operation
D
Controlled switch−off
Burner control unit LMG 21. ...
t3
Pre−ignition time approx. 12 s
t3n Post ignition time in case a
flame builds
t4
Int. time stage I II approx. 8 s
tw
Dwell time
TSA Safety time during
the sequence
Initial start−up, inspection and maintenance
approx. 12 s
2.5 s
max.
3 s
1 qW Plug−in terminals on the
burner control unit
E Fuel valve 2
G Gas pressure limiter
H Fuel valve 1
K Air pressure switch
L Ignition transformer
M Flame monitor
N External fault message
25