Checking The Nozzle Pressure - Viessmann Vitoflame 100 Service Instructions Manual

Pressure−jet gas burner. for vitoplex 100, 200 and 300. rated output 80 to 225 kw. for vitorond 200. rated output 125 to 195 kw
Table of Contents

Advertisement

Initial start−up, inspection and maintenance
Further details regarding the individual steps

Checking the nozzle pressure

12
(cont.)
1. Release the screw in test port A,
but do not remove.
2. Connect the U−shaped pressure
gauge to the test port A.
3. Open the gas shut−off valve.
4. Start the burner (see page 8).
5. Check the nozzle pressure in
accordance with the Wobbe index
and the output against the nozzle
pressure table on pages 44 to 46.
Note
During the adjustment, also check
the gas throughput by means of a
volumetric test.
6. Check and, if necessary, adjust the
nozzle pressure.
The selected gas pressure will be at
the burner approx. 10 s after the
burner start.