Viessmann Vitoflame 100 Service Instructions Manual page 7

Pressure−jet gas burner. for vitoplex 100, 200 and 300. rated output 80 to 225 kw. for vitorond 200. rated output 125 to 195 kw
Table of Contents

Advertisement

Further details regarding the individual steps
Function test without gas supply
H Check the function sequence (see
program sequence on page 25).
H Switch ON the mains isolator
(outside the installation room).
H Start the burner; for this, switch ON
the system ON/OFF switch at the
control unit.
H With the soundness test set still
connected, gently build a pressure
of approx. 20 mbar (gas shut−off
valve closed).
The following program must now
run (see also program sequence on
page 25):
When there is a heat demand
(control indicator "Demand"
illuminates at the plug−in panel), the
air damper servomotor moves from
the "Closed" position to air damper
position stage 2 and returns to
stage 1 (ST 0 − ST 2 − ST 1).
Initial start−up, inspection and maintenance
The burner control unit program
sequence is started with the
following functions:
H The burner motor starts and the
combustion chamber is purged
(approx. 30 s).
H The electric ignition is started
(pre−ignition time approx. 2 s).
H The gas solenoid valve for stage 1
opens.
H The pressure inside the valves
drops.
H The gas pressure limiter switches
the burner OFF (not a fault
shutdown).
The burner control unit enters a
fault shutdown after the expiry of a
safety interval of 2 s, if the gas
pressure limiter does not shut
down the burner.
Remove the soundness test set and
close test port A.
(cont.)
7