Adjusting The Volume Of Starting Gas - Viessmann Vitoflame 100 Service Instructions Manual

Pressure−jet gas burner. for vitoplex 100, 200 and 300. rated output 80 to 225 kw. for vitorond 200. rated output 125 to 195 kw
Table of Contents

Advertisement

Initial start−up, inspection and maintenance
Further details regarding the individual steps

Adjusting the volume of starting gas

The opening characteristics of the gas solenoid valve has been matched to
the boiler and been preset at the factory.
Generally you never need to change this setting; continue with point 3.
14
(cont.)
1. Set the quick−lift (opening
characteristics) with protective
cap G positioned upside down.
Note
Quick−lift is factory−set to "+".
Min. ionisation current 3.5 mA.
Checking the ionisation current,
see page 17.
2. Fit protective cap G.
3. Close the gas shut−off valve.
4. Remove the U−shaped pressure
gauge and close test port A (see
page 12).
¨
Danger
Check the test connector and
fittings for gas soundness.