Initial start−up, inspection and maintenance
Further details regarding the individual steps
Adjusting the volume of starting gas
The opening characteristics of the gas solenoid valve has been matched to
the boiler and been preset at the factory.
Generally you never need to change this setting; continue with point 3.
14
(cont.)
1. Set the quick−lift (opening
characteristics) with protective
cap G positioned upside down.
Note
Quick−lift is factory−set to "+".
Min. ionisation current 3.5 mA.
Checking the ionisation current,
see page 17.
2. Fit protective cap G.
3. Close the gas shut−off valve.
4. Remove the U−shaped pressure
gauge and close test port A (see
page 12).
¨
Danger
Check the test connector and
fittings for gas soundness.