Viessmann Vitoligno 200-S Installation And Service Instructions Manual page 51

High performance wood gasification boiler for split logs up to 50 cm long
Hide thumbs Also See for Vitoligno 200-S:
Table of Contents

Advertisement

Code 1
(cont.)
Boiler
Coding
Coding in the delivered condition
Flue gas temperature limit
1:...
Boiler regulates to a maximum of
the factory-set flue gas tempera-
ture.
Note
Factory setting depends on the rat-
ed boiler heating output:
20 kW: 150 °C
30 kW: 160 °C
40 kW: 170 °C
50 kW: 190 °C
Flue gas temperature minimum
2:...
Boiler regulates to a min. flue gas
temperature set at the factory.
Note
Factory setting depends on the rat-
ed boiler heating output:
20 kW: 100 °C
30 kW: 110 °C
40 kW: 120 °C
50 kW: 130 °C
Dissipate heat
44:90
Temperature in °C. If the boiler wa-
ter temperature exceeds 90 °C,
the heat is transferred to the heat-
ing circuit set in code "F3" (Heat-
ing group). For this, the boiler reg-
ulates to the max. flow tempera-
ture (code "C6", Heating group) of
the heating circuit.
Set system temperature
45:1
The min. set system temperature
can be adjusted in the menu.
O2 control active
5F:1
O
control (Lambda probe) is ena-
2
bled. It is disabled automatically in
the event of a fault.
Flue gas fan emergency mode
FB:60
If no signal from the Hall sensor is
detected, the flue gas fan is regu-
lated to 60 % of the max. speed.
Buffer maximum temperature
FC:80
At an average heating water buffer
cylinder temperature of 80 °C, the
boiler regulates to min. output.
Possible change
1:100
Max. flue gas temperature adjusta-
to
ble from 100 to 250 °C
1:250
2:100
Min. flue gas temperature adjustable
to
from 100 to 250 °C
2:250
44:50
Temperature adjustable from 50 to
to
110 °C.
44:110
45:0
The min. set system temperature is
disabled in the menu and cannot be
adjusted.
5F:0
O
control (Lambda probe) is disa-
2
bled.
FB:35
Speed for emergency mode in % of
to
the max. speed
FB:100
FC:50
Max. average temperature in °C
to
FC:100
Codes