Viessmann Vitoligno 200-S Installation And Service Instructions Manual page 47

High performance wood gasification boiler for split logs up to 50 cm long
Hide thumbs Also See for Vitoligno 200-S:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in the delivered condition
Buffer type
Buffer type:0
When heat is drawn from the buf-
fer, system temperature = temper-
ature at buffer temperature sensor
1
Only available if code "Buffer: 3, 4
or 5".
DHW
DHW:No
No DHW heating installed
DHW circulation (if heating circuit extension module installed)
DHW circula-
There is no DHW circulation con-
tion:No
nected to boiler control unit at the
heating circuit extension module.
Heating circuit 1
Heating circuit
There is no heating circuit 1 instal-
1:No
led.
Heating circuit 2
Heating circuit
There is no heating circuit 2 instal-
2:No
led.
Heating circuit 3
Heating circuit
There is no heating circuit 3 instal-
3:No
led.
Electrical ignition system
Ignition:No
No electric ignition system installed Ignition:Yes
Possible change
Buffer type:1
When heat is drawn from the buffer,
system temperature = temperature
at buffer temperature sensor 2
DHW:On the boil-
DHW heating is connected to the
er (if heating cir-
boiler control unit at the heating cir-
cuit extension
cuit extension module.
module installed)
DHW:On the mix-
DHW heating is connected to the
er module
mixer extension kit.
DHW circula-
DHW circulation is connected to
tion:Yes
boiler control unit at the heating cir-
cuit extension module.
Heating circuit
Heating circuit is connected to the
1:On the boiler (if
boiler control unit at the heating cir-
heating circuit ex-
cuit extension module.
tension module
installed)
Heating circuit
Heating circuit is connected to the
1:On the mixer
mixer extension kit.
module
Heating circuit
Heating circuit is connected to the
2:On the boiler (if
boiler control unit at the heating cir-
heating circuit ex-
cuit extension module.
tension module
installed)
Heating circuit
Heating circuit is connected to the
2:On the mixer
mixer extension kit.
module
Heating circuit
Heating circuit is connected to the
3:On the boiler (if
boiler control unit at the heating cir-
heating circuit ex-
cuit extension module.
tension module
installed)
Heating circuit
Heating circuit is connected to the
3:On the mixer
mixer extension kit.
module
Electric ignition system installed
Codes