Viessmann Vitoligno 300-C Installation And Service Instructions Manual page 99

18 to 48 kw pellet boiler
Table of Contents

Advertisement

Service functions
(cont.)
Exiting the service menu
You can leave the service menu as follows:
Checking operating states, actuators and sensors
Operating states, actuators and sensors can be
checked in the following menus:
Under "Information"
Submenu in the extended "Standard menu".
Under "Diagnosis"
Submenu in the "Service" menu.
Note
Check the temperature values or states of the indica-
ted inputs for "function and logic".
Calling up the "Information" menu
Press the following keys:
1.
"Menu" appears.
å
2.
/
for "Information".
|
~
Calling up the "Diagnosis" menu
Press the following keys:
1.
+
simultaneously for approx. 4 s.
d
å
The "Service" menu appears.
2.
/
for "Diagnosis"
|
~
Checking the outputs (actuators)
Danger
Activated charging devices (feed screw con-
veyor, screw conveyor, etc.) can cause block-
ages in the fuel discharge system during the
actuator test.
Activate charging devices only briefly.
!
Please note
Incorrectly connected actuators can cause dam-
age to the system.
During the actuator tests, check the respective
actuator carefully.
Diagnosis and service checks
By pressing
ä
Automatically after 30 minutes
Via menu point "Terminate service"
Examples of "function and logic":
Are the temperature values of the sensors in the nor-
mal range?
Is the state of the maintenance cover (open or
closed) correct?
Is the state of the light barrier (free or interrupted)
correct?
Residual oxygen content OK?
3.
d
to confirm.
4.
/
+
for the required information in the
d
|
~
menu.
5.
until the default display is shown.
ä
3.
d
to confirm.
4.
/
+
for the required information in the
d
|
~
menu.
5.
until the default display is shown.
ä
!
Please note
Overheating can damage the ignition element.
The required air supply is removed from the igni-
tion element by opening the combustion cham-
ber door or cover.
Always ensure that the combustion chamber
door and the covers on the boiler are closed
during start-up and heating operation.
The following displays appear in sequence:
"General"
"Boiler"
"Charging"
"Additional boiler"
"Heating circuit 1"
99