Viessmann Vitoligno 300-C Installation And Service Instructions Manual page 96

18 to 48 kw pellet boiler
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Frost protection temperature
A3:2
Outside temperature below 1 °C:
Frost protection function "On"
Outside temperature above 3 °C:
Frost protection function "Off"
!
Please note
If the frost protection temperature is set to less
than 1 °C outside temperature, uninsulated
pipes may freeze.
There is a particular risk for outdoor pipes and in
standby mode, e.g. during holidays. Provide
pipes with thermal insulation and avoid unsuper-
vised standby mode.
Parameter address
Frost protection function / heating cir-
"A3"
cuit pump "On"
9
10 °C
8
9 °C
7
8 °C
6
7 °C
5
6 °C
4
5 °C
3
4 °C
2
3 °C
1
2 °C
0
1 °C
1
0 °C
2
1 °C
to
to
15
14 °C
Coding
Coding in the delivered condition
Frost protection activate
A4:0
The frost protection function is ac-
tivated. Start and stop tempera-
tures of the function can be adjus-
ted (code "A3", "Heating" group).
Frost protection function: The heat-
ing circuit pump is switched on at
the relevant outside temperature; a
min. flow temperature of 10 °C is
specified. At the relevant outside
temperature, the frost protection
function is automatically switched
off.
96
Possible change
A3:-9
Frost protection function "On"/"Off"
to
See the following table:
A3:15
Frost protection function / heating circuit
pump "Off"
8 °C
7 °C
6 °C
5 °C
4 °C
3 °C
2 °C
1 °C
0 °C
1 °C
2 °C
3 °C
to
16 °C
Possible change
A4:1
The frost protection function is deac-
tivated. Adjustment only possible if
code "A3:−9" has been set.
Note
Observe the note for code "A3".