Summary of Contents for Biasi RINNOVA ADAPTIVE M300V.2025 SM
Page 1
Wall hung, fanflue, roomsealed, high efficiency gas boiler Service manual RINNOVA ADAPTIVE Models G.C. Appl. No. M300V.2025 SM 47-583-46 COMBI BOILER M300V.2530 SM 47-583-47 COMBI BOILER M300V.3035 SM 47-583-48 COMBI BOILER Leave this manual adjacent to the gas meter Warning: Service / repairs must be carried out, only by a qualified Gas Safe Registered Engineer, who will be responsible for the current Regulations for gas appliances.
GENERAL ACCESS AND EMPTYING HYDRAULIC CIRCUITS GENERAL ACCESS AND EMPTYING Pull the lower part of the front panel and lift it upwards (Figure HYDRAULIC CIRCUITS 2.3). 2 .1 Nomenclature Figure 2 .3 To remove the side panels loosen the screws "B" (Figure 2.2) and "C"...
GENERAL ACCESS AND EMPTYING HYDRAULIC CIRCUITS 2 .4 Main electronic p .c .b . box Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- nent . Terminal block lid removal To gain access to the parts located inside the control panel pro- ceed as follows: 1 Remove the front panel of the case.
GENERAL ACCESS AND EMPTYING HYDRAULIC CIRCUITS 2 .5 Emptying the primary circuit 2 .6 Emptying the D .H .W . circuit 1 Close the C.H. circuit flow and return cocks "M" (Figure 2.10). 1 Close the D.H.W. inlet cock "N" (Figure 2.10). 2 Open one or more hot water taps until the boiler has been completely emptied.
DIAGRAMS 3 .2 Circuit voltages during C.H. or D.H.W. operation Electrical voltages or frequency only during C.H. operation with burner on only during D.H.W. operation 3 way Safety D.H.W. Main circuit Supply network diverter valve Pump thermostat Flow switch pressure switch Gas valve Figure 3 .2 - 9 -...
FAULT FINDING 4 .1 Display diagnostic Primary limitation in D.H.W. mode. The display indications provide help in the diagnosis of fault find- Maintenance required. ing. The wrench symbol is flashing (without show- The control panel display gives other information for the user. ing any error). The following table gives fault code, error and the reson for the fault.
Page 14
FAULT FINDING Figure 4 .5 6 Pressing keys "A" or "C" makes it possible to change the value of parameter 34 from 0 to 48 months. It is possible to set parameter 34 to 99 thereby disabling the maintenance request (symbol will disappear from the display).
CONDENSING HEAT EXCHANGER CONDENSING HEAT EXCHANGER 5 .1 Function The Condensing heat exchanger "A" in Figure 5.1 has the func- tion of transferring heat produced from combustion of the gas and from the flue exhausted gas to the water circulating in it. Figure 5 .1 By reducing the combustion products temperature, the latent heat of the vapour is transferred to the water circuit, allowing an extra gain of useful heat.
CONDENSING HEAT EXCHANGER 5 .3 Cleaning If there are deposits of dirt on the coil of the Condensing heat exchanger, clean with a bristle paintbrush and remove the dust with a hoover. Warning: After cleaning or replacement as detailed above, it is deemed necessary to undertake a com- bustion analysis as detailed in chapter "11 .3 Adjust- ment - Chimney Sweep Function"...
D.H.W. HEAT EXCHANGER D .H .W . HEAT EXCHANGER 6 .1 Function The D.H.W. heat exchanger "A" in Figure 6.1 and Figure 6.3 al- lows the instantaneous transfer of heat from the primary hydrau- lic circuit to the water destined for D.H.W. use. Figure 6 .3 6 Move the exchanger towards the rear of the boiler and extract it to the left.
PUMP PUMP 7 .2 Removal pump head 7 .1 Function Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- The pump "A" in Figure 7.1 and Figure 7.2 has the function of nent . making the water in the main circuit circulate through the main condensing heat exchanger and therefore through the C.H.
THREE WAY DIVERTER VALVE THREE WAY DIVERTER VALVE 8 .1 Function The diverter valve "A" (Figure 8.1) has the function of modifying the hydraulic circuit of the boiler by means of an electric com- mand given by the electronic control p.c.b. in order to send the water that exits the primary heat exchanger towards the C.H.
THREE WAY DIVERTER VALVE Warning: Please note the electric actuator is ener- 5 Unscrew the connector "H" (Figure 8.6), the C.H. flow con- gized 240VAC even if the boiler is in a standby con- nector and the D.H.W. outlet connector. dition . 6 Remove the D.H.W. heat exchanger (see "6.2 Removal" on page 17).
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. MAIN ELECTRONIC CONTROL/IGNITION The fundamental function of the Main electronic control/ignition P .C .B . p.c.b. is that of controlling the boiler in relation to the external needs (i.e. heating the dwelling or heating the water for D.H.W. use) and operating in order to keep the temperature of the hy- 9 .1 Function draulic circuits constant.
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. Normally, the result of the comparison between these two signals directly operates the fan speed adjusting the useful output gen- erated in order to stabilize the temperature of the exiting water. If during the D.H.W. mode operation, the temperature of the pri- mary circuit goes over 90°C, the useful output is automatically reduced so that the primary circuit cannot reach excessive tem- peratures.
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. PARAMETER DIGIT VALUES PARAMETER DIGIT VALUES Boiler model/type External relay operating mode 1 (0=OFF, 1=Zone by remote, 2=Alarm) Type of gas External relay operating mode 2 User interface (0=OFF /TA2=OFF, 1=Zone heat. 2 / Type of domestic hot water exchanger TA2 active, 2= EVG ext / TA2 Active, 3= Anomaly / TA2 Active, 4 =Remote filling Type of primary circuit control device...
Page 25
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. 1 Remove all the body panels (see section "2.2 Case panels" on page 5). 2 Gain access to the parts located inside the Main electronic p.c.b. box as explained in the section "2.4 Main electronic p.c.b. box" on page 6 of this manual. 3 Unscrew the screws "D"...
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. 9 .7 Thermal control in the mode Switch in the function mode Taking circulator off water from the domestic hot circulator on fan still water circuit? Is primary circuit Main circuit pressure stop circulator (3min) temperature higher than that switch consense? selected? lock memorised?
MAIN ELECTRONIC CONTROL/IGNITION P.C.B. 9 .8 Thermal control in the mode Switch in the function mode See functioning with the function Taking Request for heat from water from the domestic hot control in the mode room thermostat? water circuit? (sec. 9.7) circulator off fan still circulator on...
CONTROL PANEL ELECTRONIC P.C.B. 10 CONTROL PANEL ELECTRONIC P .C .B . SIGNAL DISPLAYED BY THE LCD FUNCTION 10 .1 Function E01 + Safety lockout due to failed ignition. E02 + Lockout due to safety thermostat. E03 + Generic lockout. Pump circulation failure, insufficient system E04 + pressure or water pressure sensor not con-...
Page 29
CONTROL PANEL ELECTRONIC P.C.B. FUNCTION FUNCTION Anomaly due to probable chimney obstruc- E24 + If the pressure is not correct the value is tion displayed with the flashing symbol. Flame loss for more than 6 consecutive E25 + times. Next maintenance due date (factory setting 12 months).
Page 30
CONTROL PANEL ELECTRONIC P.C.B. FUNCTION Delay burner ignition due to system setting (flashing uu + flashing temperature). Boiler in chimney sweep function. To activate the chimney sweep function, set "parameter P32=1 ... 4". The following is displayed: LP = minimum D.H.W. hP = minimum output in heating mode cP = maximum output in heating mode dP = maximum D.H.W.
GAS VALVE 11 GAS VALVE 11 .3 Adjustment - Chimney Sweep Function Warning: isolate the boiler from the mains electrici- 11 .1 Function ty supply before removing any covering or compo- nent . The gas valve "A" in Figure 11.1 controls the gas inflow to the boiler burner.
GAS VALVE 13 Open at least one hot water tap fully. function” is at maximum output in domestic hot water mode (Figure 11.8). Warning: If the boiler has a correct CO reading in LP but is incorrect CO in dP before adjusting the boiler ensure the supply pressure is within accept- able limits! Figure 11 .4...
GAS VALVE Pin 1 and 3 = 25 Ohm * 5 To enter in the parameters setting mode press at the same time the 2 keys "H" and "J" (Figure 11.9) and hold in for 5 second until the display shows Figure 11.10. Pin 2 and 4 = 65 Ohm * *at ambient temperature.
Page 34
GAS VALVE 7 Remove the brass plug and turn the plastic screw inside it fully clockwise until it stops. Do not overtight. 8 Turn it counter-clockwise 2 and 3/4 turns. 9 Adjust the gas valve using the flue analyser as described in section "11.3 Adjustment - Chimney Sweep Function"...
PRIMARY CIRCUIT FLOW SWITCH 12 PRIMARY CIRCUIT PRESSURE SWITCH 12 .2 Removal Warning: isolate the boiler from the mains electrici- 12 .1 Function ty supply before removing any covering or compo- nent . The Primary circuit pressure switch ("A" in Figure 12.1) function is to check the presence of water in the primary hydraulic circuit 1 Remove the front and right hand side panels of the case, turn and that the pressure is above the minimum.
EXPANSION VESSEL AND PRESSURE GAUGE 13 EXPANSION VESSEL AND PRESSURE 13 .3 Removal of the expansion vessel GAUGE Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- 13 .1 Function nent . The Expansion vessel ("A" in Figure 13.1) function is to allow 1 Remove the front and right hand side panels of the case, turn for the volume expansion of the C.H.
D.H.W. FLOW SWITCH, FILTER AND FLOW LIMITER 14 D .H .W . FLOW SWITCH, FILTER AND 14 .3 Removal of the sensor FLOW LIMITER Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- 14 .1 Function nent .
D.H.W. FLOW SWITCH, FILTER AND FLOW LIMITER 14 .5 Removal of the flow switch group and D.H.W. circuit filter Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- nent . 1 Please remove the sensor first as previously described and ensure it remains dry. 2 Remove the front panel of the case and empty the D.H.W.
TEMPERATURE PROBE 15 NTC HEATING DELIVERY PROBE - 15 .2 Checks NTC MAXIMUM TEMPERATURE, C .H . Temperature-resistance relationship TEMPERATURE RETURN PROBE NTC, D .H .W . TEMPERATURE PROBE NTC Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- 15 .1 Function nent .
TEMPERATURE PROBE Warning: to lubricate the O-ring gaskets exclusively use a silicone base grease compatible to be in con- tact with foods and approved by the local water Au- thorities . Figure 15 .5 Figure 15 .4 15 .5 Removal of the D .H .W . temperature probe Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- nent .
BY-PASS VALVE 16 BY-PASS VALVE reversing the order of removal. 16 .1 Function Warning: to lubricate the O-ring gaskets exclusively The By-pass valve "A" in Figure 16.1 is located between the C.H. use a silicone base grease compatible to be in con- water flow and return and its function is that of guaranteeing a tact with foods and approved by the local water Au- minimum flow across the primary heat exchanger if the circula-...
FAN AND AIR BOX 17 FAN AND AIR BOX 17 .1 Function The function of the Fan "A" (Figure 17.1) is to force the mixture of air and gas into the burner. The function of the Air box "B" is to mix the gas and the air in the right proportion.
IGNITION AND DETECTION ELECTRODES 18 IGNITION / DETECTION ELECTRODE 3 Unscrew the screws "B" and remove the electrode "A". AND BURNER 4 Assemble the ignition / detection electrode carrying out the removal operation in reverse order. 18 .1 Function The ignition / detection electrode "A" is fitted on the left side of Warning: A new sealing gasket must be used during the fan-burner group "D".
IGNITION AND DETECTION ELECTRODES 18 .6 Checks Check of the spark generator. Warning: isolate the boiler from the mains electrici- ty supply before removing any covering or compo- nent . Burner gasket There is not a significant way to verify the integrity of the spark generator. When the fan turns but the burner does not light a Burner possible cause is a faulty spark generator and it is advisable to replace it to locate the fault.
Page 45
IGNITION AND DETECTION ELECTRODES Excessive exposure to these materials may cause temporary ir- ritation to eyes, skin and respiratory tract. Known hazards - Some people can suffer reddening and itching of the skin. Fibre entry into the eye will cause foreign body irrita- tion, which can cause severe irritation to people wearing contact lenses.
FLUE TEMPERATURE PROBE NTC AND SAFETY THERMAL FUSE 19 FLUE TEMPERATURE PROBE NTC AND In case of intervention of this safety device the heat exchanger SAFETY THERMAL FUSE (part shown in Figure 19.3) may be damaged and must be re- placed.
CONDENSATE TRAP 20 CONDENSATE TRAP 20 .3 Removal Warning: isolate the boiler from the mains electrici- 20 .1 Function ty supply before removing any covering or compo- nent . The condensate trap "A" in Figure 20.1 and Figure 20.2 allows the discharge of the condensate via the condensate drain pipe 1 Remove the front and right case panels.
SHORT SPARE PARTS LIST 21 SHORT SPARE PARTS LIST G .C . part no . Description Q .ty Manufacturer part no . Burner (mod. M300V.2025 SM) BI1713 100 Burner (mod. M300V.2530 SM - M300V.3035 SM) BI1713 101 Expansion vessel BI1462 100 Condensing heat exchanger (mod.
Page 50
SHORT SPARE PARTS LIST Figure 21 .1 - 50 -...
Page 52
*1796234660* 17962.3466.0 4221 52A4 Biasi UK Ltd Commercial Road Leamore Enterprise Park WALSALL WS2 7NQ Sales Tel. 01922 714600 Tech. Service Tel. 01922 714636 www.biasi.co.uk...