Figure 5.38
• Press button 14 (Figure 5.33) to confirm the val-
ue entered. The display will show the following
(Figure 5.39) for 5 seconds, then move up to
the next level.
Figure 5.39
• Press the keys 13 and 15 simultaneously (Fig-
ure 5.33) to exit the level without changing the
value (return to the previous level).
To exit the parameters menu:
• wait 15 minutes without pressing any key;
• switch off the electric power supply;
• press the 13 and 15 keys simultaneously for 5
seconds (Figure 5.33) (return to previous level).
At this point the system delivery temperature
will follow the trend in relation to the set K co-
efficient.
If the room temperature is not comfortable, you
can increase or decrease the heating system de-
livery temperature by ± 15°C using the 15 (de-
crease) and 16 (increase) buttons (Figure 5.33).
INSTALLATION
Delivery
temperature °C
80
70
60
50
40
30
20
20
Figure 5.40
The temperature trend when changing the set-
ting using keys 15 and 16 for a K 1.5 is shown in
Figure 5.40.
Sequence for setting the K coefficient with the
remote connected
Access REMOTE programming and the K coeffi-
cient setting can be selected.
• Power the boiler by turning on the two-way
switch fitted during installation.
• Press button
ter
Figure 5.41
Press
5.42).
+ 15 °C
K = 1,5
-15 °C
15
10
5
0
-5
External temperature °C
for more than 3 seconds to en-
mode (Figure 5.41).
0
21
3
1
8
6
9
1 5
1
2
to display the K REG window (Figure
-10 -15 -20 -25
- 53 -