Related Parameters - YASKAWA A1000 Installation Manual

Motor pg feedback line driver interface
Hide thumbs Also See for A1000:

Advertisement

6 Related Parameters

6
Related Parameters
The following parameters are used to set up the drive for operation with the option. Set
parameters as needed. Parameter setting methods can be found in the drive Quick Start
Guide or Technical Manual.
No.
Name
(Addr. Hex)
Control
A1-02
Method
(102)
Selection
F1-01
PG 1 Pulses
(380)
per Revolution
<2> <3>
PG Feedback
F1-02
Loss Operation
(381)
Selection
PG Overspeed
F1-03
Operation
(382)
Selection
PG Deviation
F1-04
Operation
(383)
Selection
22
Table 6 Related Parameters
Description
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Sets the pulses to be read from the pulse generator.
Sets the stopping method when the PG becomes
disconnected (PGo).
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
4: No alarm display
Note: Due to potential damage to the motor and
machinery, only use the "Continue running" and "No
alarm display" settings under special circumstances.
Sets the stopping method when overspeed is
detected.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
Note: Due to potential damage to the motor and
machinery, only use the "Continue running" setting
under special circumstances.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
Note: Due to potential damage to the motor and
machinery, only use the "Continue running" setting
under special circumstances.
YASKAWA ELECTRIC TOBP C730600 37B 1000-Series Option PG-X3 Installation Manual
Control
Values
Method
Default:
<1>
All Modes
Range:
<1>
V/f w/ PG
Default:
<1>
CLV
Min:
<1>
CLV/PM
Max:
<1>
V/f w/ PG
Default: 1
CLV
Range:
<1>
CLV/PM
V/f w/ PG
Default: 1
CLV
Range: 0 to 3
CLV/PM
V/f w/ PG
CLV
Default:
<1>
CLV/PM
Range: 0 to 3
AOLV/PM

Advertisement

loading

This manual is also suitable for:

L1000a