Installation Instructions
1. Entry Delay No. 1 and No. 2 (fields
for UL Residential Burglar Alarm installations, and entry delay plus dial delay
should not exceed 1 minute. For UL Commercial Burglar Alarm installations,
total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar
Alarm installations with line security, total exit delay time must not exceed 60
seconds. For UL Burglar Alarm installations without line security (Grade A),
total exit delay time must not exceed 120 seconds.
3. The maximum number of reports per armed period (field
(unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for
UL installations (Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard
by all partitions.
9. For UL commercial burglar alarm installations the control unit must be
protected from unauthorized access. The tamper switch installed to protect the
control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended
downloading) is not permitted for UL installations.
11. Auto-disarming is not a UL Listed feature.
8-4
UL NOTICES
Q
Q
35,
36) cannot be greater than 30 seconds
Q
93) must be set to "0"