Installation Instructions
FIELD
TITLE and DATA ENTRIES
Event Log Full Report Code
*89
0 = disable; 1-F = see description above ∗59
Event Log Enables
*90
0 = no event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of
entries)
Option Selection
*91
0 = none
4 = using Audio Alarm Verification (AAV) unit
8 = Enable Exit delay restart/reset ††
Multiple choice example: for both AAV and
Exit delay restart, enter # + 12 (4 + 8).
UL
UL installations using the AAV
feature must use the ADEMCO UVCM
module (part of the ADEMCO UVS
system).
Exit Delay Restart/Reset must be disabled.
Telecom Monitor Enable
*92
Entry 1–Timeout:
0 = disabled
1-15 = 1 minute to 15 minutes respectively
(2 = 2 min, 3 = 3 min, etc.; # + 10 =10 min, #
+ 11 = 11 min, # + 12 = 12 min, # + 13 = 13
min, # + 14 = 14 min, # + 15 = 15 min)
Entry 2–Display/Sound:
0 = keypad display only when phone line is
faulted.
1 = keypad display plus keypad trouble
sound when line is faulted. Each
partition turns off its own trouble sound.
No automatic timeout.
2 = Same as "1" plus programmed output
device STARTS. If any partition is
armed, external sounder activates.
External sounder will be turned off by
normal siren timeout or by security code
plus OFF from any partition (it does not
have to be the one that was armed).
No. of Reports In Armed Period
*93
per Zone (Intermittent Sensor
Suppression)
0 = unlimited number of reports
1-6 = 1 to 6 report pairs per zone per armed
period
Download Phone Number
*94
Enter up to 30 digits as follows: 0–9, # +11
for "∗", # + 12 for "#", # + 13 for a pause.
4-8
EXPLANATION
If an Event Logging selection is made in field ∗90, a message can be
sent to the central station receiver when the log is 80% full. If the log
becomes full, new messages overwrite the oldest messages in the log.
This system has the ability to record up to 250 events in a history log.
At any time, the downloader operator can then upload the log and view
or print out all or selected categories of the log. The downloader
operator can also clear the log. Event log can also be viewed at an alpha
keypad (see User Guide for log display format).
The display/printout at the central station will show the date, time,
event, and description of the occurrences.
Data Entry Example: To select Alarm/Alarm Restore" and "Open/Close",
enter 9 (1+ 8); to select all events, enter #15.
Select the desired options by adding the values of each desired option.
††"Exit Delay Restart/reset" option allows use of the [∗] key to restart
the exit delay at any time when the system is armed STAY or
INSTANT. This feature also enables automatic exit delay reset, which
resets exit delay if the entry/exit door is re-opened and closed before exit
delay time expires after arming AWAY or MAXIMUM.
IMPORTANT: AAV should not be used when Paging or Alarm Reports
are sent to a secondary number unless the monitoring zone option is
used (which pauses calls). Otherwise, the call to the secondary number
by the communicator after the alarm report will prevent the AAV from
taking control of the telephone line, and the AAV "Listen in" session
cannot take place.
Entry 1: Sets the length of time a phone line fault must remain after
detected before the second digit option is activated.
Entry 2: Selects the desired phone line fault response.
Option 2 may be used even if a relay unit or Powerline carrier device
is not connected to the control.
Programmed Output Device must either be programmed to be
STOPPED in field ∗80 or STOPPED by entry of [security code] + [#] +
8 + device number. Partition in ∗80 should be set to "0," for STOP.
UL
Field *92 must be enabled for fire alarm installations, UL
commercial burglar alarm installations and UL residential burglar alarm
installations.
If the control unit is used on a UL commercial burglar alarm system
which requires 2 methods of remote communication, then the control
unit's DACT and the other method of signal transmission must monitor
each other against communication failure and line fault. The fault must
be received and annunciated within 200 seconds of its occurrence.
This option can be used to limit the number of alarm/alarm restore
messages per zone sent to the central station in an armed period.
UL installations must be 0 (unlimited reports).
Enter the phone number of the downloading computer.
Do not fill unused spaces. End field by entering ∗. To clear entries
from field, press ∗94∗.