Go/No Go Test Mode; Automatic Standby Battery Tests - Honeywell ADEMCO VISTA-48D Installation And Setup Manual

Table of Contents

Advertisement

Installation Instructions
NOTES:
• All BR type RF units (e.g., 5804) must physically be activated to clear the display.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on
that transmitter are cleared. This also applies to multiple-loop transmitters (e.g. 5816 and 5817).
• Any transmitter not "enrolled" or any zone that is not faulted will not turn off its zone number.

Go/No Go Test Mode

The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and
allows you to reorient or relocate transmitters if necessary, before mounting the transmitters
permanently. This mode is similar to the Transmitter Test mode, except that the wireless receiver
gain is reduced. This will enable you to make sure that the RF signal from each transmitter is
received with sufficient signal power when the system is in the normal operating mode.
1. Enter [Installer code] + [#] + 4 from the partition being tested. Repeat this test for each partition.
2. After you have placed transmitters in their desired locations and the approximate length of wire to
be run to sensors is connected to the transmitter's screw terminals (if used), fault each transmitter.
Do not conduct this test with your hand wrapped around the transmitter.
a. Keypad beeps three times to indicate signal reception and displays the appropriate zone number.
b. If the keypad does not beep, you should reorient or move the transmitter to another location.
Usually a few centimeters in either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then
permanently mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: [Installer code] + OFF.
Dialer Communication Test
1. Enter Installer Code + 5 [ TEST ], then press "1" at the prompt to start the Dialer Test.
1=DIAL, 0=WALK
The following will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY
If the dialer test is unsuccessful, the following is displayed:
COMM FAILURE
2. Enter installer code + OFF to clear the display and exit.

Automatic Standby Battery Tests

1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and
properly connected. If a battery is not present or is not properly connected, a "LOW BATTERY"
message is displayed and, if so programmed, will be reported to the central station.
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours
after exiting the Programming mode or after powering up the system. In addition, entry into the
Test mode will also cause a battery capacity test to be initiated. If the battery cannot sustain a load,
a "Low Battery" message is displayed and, if so programmed, will be reported to the central station.
7-2
(no special display on Fixed-Word keypads)
("Cd" displayed on Fixed-Word Display Keypads)
A Contact ID report will also be sent (code 601)
("FC" displayed on Fixed-Word Display Keypads)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents