Programming Field Settings for UL864 Compliance ..................7 Programming Field Settings for ULC304 Compliance .................. 10 Section 1: General Description ....................11 SIA Installations ............................... 11 About the VISTA-32FBPT ..........................11 Features ................................11 Guidelines for Wiring a System ........................15 Section 2: Partitioning ........................17 Theory of Partitioning ............................
Page 4
Testing Wireless Transmitters ........................71 Trouble Conditions ............................72 To the Installer ..............................73 Section 8: Using the Vista-32FBPT as a Slave Communicator ..........75 Wiring ................................75 Programming ..............................75 Sending Vista-32FBPT System Troubles to the Fire Alarm Panel ............... 76 Appendix A: Regulatory Agency Statements ................
1 = YES 0 = NO 0 ∗ ∗ ∗ ∗ Additional system options are programmed via data fields, which are indicated by a “star” (∗) followed by the data field number. PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent Honeywell products.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Requirements The VISTA-32FBPT control panels provide features that allow the system to meet UL864 Commercial Fire requirements. To meet these requirements, follow the guidelines outlined in this section.
Page 8
Possible settings Program feature or option Permitted in Settings permitted in UL864? Y/N UL 864 0 = disable Must be set to “1” (enable). ∗ 28 POWER-UP IN PREV. 1 = enable STATE 0 = disable Must be set to “0” for all ∗...
Page 9
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N 0 = disable Must be set to “0” (disable) for ∗ 45 EXIT DELAY 1 = enable partition 1. SOUNDING (PARTITION SPECIFIC) 0 = none Not used.
Possible settings Program feature or option Permitted in Settings permitted in UL 864 UL864? Y/N 0 = disable Must be set to “1” (enable). ∗ 01 EVENT DISPLAY LOCK 1 = enable 0 = disable Must be set to “0” (disable). ∗...
The VISTA-32BPT is not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields. About the VISTA-32FBPT The VISTA-32FBPT is a 2-partition, UL Listed commercial fire and burglary control panels that include the features described below. Features Hardwire and Optional Expansion Zones Provides 8 hardwire zones.
Page 12
Output/Relay Devices 4204 and 4204CF Relay Modules, and 4101SN V-Plex Relay Modules can be used to program up to 96 outputs. • Outputs can be activated in response to system events (alarm condition), at a specific time of day, at random times, and manually using the #70 Relay Command Mode.
Page 13
Access Control Supports 8 VistaKey modules single-door access control modules • Supports up to 250 access cards. • Can store access control events in the event log. • The access control function is not Listed for use in UL Commercial Fire Installations. System Communication Supports approved ECP Communication Devices that can send Contact ID messages (e.g., Alarmnet GSM, i- •...
Page 14
Provides trigger outputs, which may interface with Communication equipment or other devices such as a • keyswitch, a Honeywell access control system, or an automation system. • Provides an option to have trouble and supervisory conditions automatically clear from the display when the zone returns to the ready/normal state (entry of Code + OFF is not required).
Guidelines for Wiring a System The installer must keep certain guidelines in mind while installing a system. The Vista-32FBPT contains • an ECP bus and a polling loop bus for connecting Fire and Burglary devices. When installing both Commercial Fire and Burglary devices, all Fire devices must be isolated from the Burglary devices on each bus.
Section 2: Partitioning • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Theory of Partitioning This system provides the ability to arm and disarm up to two different areas, as if each had its own control.
Page 18
1∗ ∗ ∗ ∗ 18 Affects Lobby (must be programmed by partition) Setting this field to 1 for a specific partition causes that partition to affect the operation of the common lobby as follows: When the first partition that affects the lobby is disarmed, the lobby is automatically disarmed. The common lobby cannot be armed unless every partition selected to affect the lobby is armed.
Master keypads for the system. Assigning any keypad to Partition 3 in Device Programming in the #93 Menu Mode (Vista-32FBPT Programming Guide) makes that keypad a Master keypad. A Master keypad reflects the status of the entire system (Partitions 1-2) on its display at one time.
Page 20
The following is a typical display: S Y S T E M 1 2 S T A T U S R N Possible status indications include: A = Armed Away S = Armed Stay M = Armed Maximum C = Comm Fail I = Armed Instant R = Ready N = Not Ready...
This section describes the procedures for mounting and wiring the control panel and all the peripheral devices. Mounting the Control in the Standard Cabinet for Commercial Fire only Applications If you are installing a Vista-32FBPT in the Fire-only cabinet with the internally-mounted transformer, follow the steps below.
TELCO LINE DETAIL A NOT TO SCALE ZONE MAKE SURE THAT BELL WIRING TERMINAL 2 (XFMR SECONDARY WIRE) AND TERMINAL 3 (BELL WIRE) ARE TERMINATED AS FUSE SHOWN TO MAINTAIN 1/4" MIN. SPACING. TIE WRAP TO CABINET NOTE: NON POWER-LIMITED BATTERY BATTERY WIRING (AC, BATTERY) MUST...
Mounting the Control in the Attack-Proof Cabinet (Suitable for Commercial Fire/Commercial Burglary Applications) If you are installing a Vista-32FBPT in the attack-proof cabinet with the external transformer, follow the steps below. Step Action Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
For safe and vault installations, a Listed tamper switch, must be installed on the cabinet backbox to protect the • cabinet from being removed from the wall. This device must also be connected to zone 6. Commercial Fire Guidelines For Commercial Fire installations, the following requirements apply (See Figure 3-5). System components mounted inside the cabinet must be placed so that all power-limited wiring is separated from all •...
CABINET PLATE DETAIL B INSTALLING NYLON STANDOFFS (2) CABINET PLATE CABINET PLATE PC BOARD MOUNTING SPACER SCREW DETAIL A SIDE VIEW DETAIL C ATTACHMENT SIDE VIEW, PC BOARD INSTALLATION USING SPACERS (3) AND MOUNTING SCREWS (3) fire_burg_cab-002-V1 Figure 3-6: Mounting the PC Board in Attack-Proof Cabinet Installing the Keypads Up to 31 addressable keypads (addresses 00-30) may be used.
Commercial Fire Requirements For commercial fire installations, the primary fire keypad must be installed on panel Keypad Port 2 and mounted within 20 feet of the control panel. External wiring must be run in conduit. Additionally, you can install supplemental fire keypads and devices on ECP Port 1, using an ECP Isolator to separate all fire wiring from all burglary wiring (see Figure 3-8).
Selectable for no timeout or timeout of 2-30 minutes. • You may use a Commercial Fire Listed 24VDC Power Supply to convert one or both VISTA-32FBPT 12VDC, 1.7A style-Y supervised Special Application Notification Appliance Circuits to 24V, style-Y supervised, Special...
Page 28
(972 Earth Ground). The VISTA-32FBPT indicates the trouble condition regardless of whether the system is armed or disarmed. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1.
Page 29
ALARM INDICATING DEVICE TYPE MANUFACTURER MODEL # 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red SYSTEM SENSOR 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red SYSTEM SENSOR P4RH 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor SYSTEM SENSOR P4RK 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor SYSTEM SENSOR P4RHK...
Install a 2K EOL resistor (Model 2EOL, supplied) across the last notification appliance on each Notification Appliance Circuit to be supervised. Auxiliary Relay Connections The VISTA-32FBPT provides a built-in Form C relay with contacts rated at 28VAC/VDC, 2.8A. The relay may be programmed (field 3 61) for one of the following functions: ∗...
Figure 3-11: Wiring Auxiliary Relay for Smoke Detector Reset Telephone Line Connections The VISTA-32FBPT provides one main built-in dialer for communication to the central station and one optional 5140DLM Backup Dialer, both supervised for voltage and current on the phone lines...
• For Listed fire central station (UL864/NFPA 72) applications, use communications device 7847i alone, the main dialer with the 7847i or use the main dialer with the 5140DLM. For listed fire remote station (UL864/NFPA 72) applications, use the main dialer with the 5140DLM. •...
429AT * This model may not be used on zones designated as Zone Type 16: Fire with Verification. These smoke detectors are UL Listed for use with the VISTA-32FBPT and are the only 2-wire smoke • detectors that may be used.
Wiring 2-Wire Smoke Detectors to Zones 1 and 2 2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the last detector. To wire 2-wire smoke detectors to zone 1 and/or zone 2, perform the following steps: Step Action Select 2-wire smoke detectors from the list of compatible detectors.
Zone 6 Tamper Configuration Zone 6 may be used as a tamper loop for the VISTA-32FBPT Cabinet Door Tamper Switch. Assign zone 6 to a burglary partition. Program it for day trouble/night alarm (zone type 5) when only one burglary partition is used.
No more than 64mA may be drawn on any individual wire run. • The 4190SN right loop must not be used, and the left loop must be EOLR-supervised. • The 4297 must be powered from the VISTA-32FBPT Auxiliary Power Output.
Refer to Figures 3-17 and 3-18, to follow. DO NOT use the 4197 Polling Loop Extender module with the VISTA-32FBPT. Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load on the panel’s power supply.
Wireless Zone Expansion The 5881ENHC RF Receiver, 5869 Holdup Switch Transmitter and 5817CB Wireless Commercial Household Transmitter are Listed for Commercial Burglary applications. All other RF receivers and transmitters are not listed for UL Commercial Burglary applications. U LC Wireless devices cannot be used for ULC Commercial Fire Installations. The following table lists the receivers that may be used and the number of zones they support.
Installation and Setup of the 5881ENHC RF Receiver Take note of the address you select for the RF receiver, as this address must be enabled in the system’s Device Programming in the #93 Menu Mode. To install the 5881ENHC RF receiver, perform the following steps: Step Action Mount the receiver, following the advisories stated previously.
ANTENNAS TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. EACH RECEIVER MUST BE ON INDIVIDUAL HOME RUN. INSERT IN USE MAX. of 220 ft. [67m of #22 (0.64mm) CIRCUIT RIGHT-HAND WIRE or 550 ft. (168m) of #18 (1mm) WIRE BOARD TERMINALS FOR EACH RUN. OBSERVE 20 ft. MAX. FOR COMMERCIAL FIRE INSTALLATIONS.
Installing Output Devices The VISTA-32FBPT supports up to 96 outputs. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). The 4204, 4204CF, and/or 4101SN may be used as output devices.
Step Action Connect the module’s wire harness to the control (11, 12, 13 and 14). Plug the connector on the harness to the module. When mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths.
Connect the device to the polling loop, terminals 28 (+) and 29 (-). Be sure to observe polarity. Installing a Remote Keyswitch A UL-Listed remote keyswitch, such as the Honeywell 4146, can be used for remote arming/disarming of the burglary part of the system and for silencing alarms. The keyswitch operates in only one particular partition.
Wiring for the Remote Keyswitch To install the ADEMCO 4146 keyswitch, perform the following steps: Step Action Connect the ADEMCO 4146 to the panel as shown in Figure 3-23. If you are using the tamper, make sure it is connected to a zone. (ARMED) (READY) GREEN...
11 is not, zone 10 will report via the communications device, but zone 11 will not. Messages are transmitted from the VISTA-32FBPT to the communications device on a “first in/first out” basis. If events occur at the same time, they are transmitted in order of priority. The priority from most to least important is : Fire Alarms, Panic Alarms, Burglary Alarms, Fire Troubles, Non-Fire Troubles, Bypasses, Openings/Closings, Test messages, and all other types of reports.
If split reporting is selected for the VISTA-32FBPT, then the communications device will send the appropriate reports to the primary and secondary central stations. Installing the Communicator To install the communications device, perform the following steps: Step Action Mount the communicator according to the instructions that accompany the Communicator.
Page 48
Local +12V or +24V supply lead to the N/C relay terminal 11 (if a mag lock is being used), OR to the N/O relay terminal 10 (if a door strike is being used). Connect the (–) polling loop and (+) polling loop leads (from the VISTA-32FBPT) to terminals 4 and 3, respectively.
14V MAX (12V @ 85-160mA Nominal) POLLING LOOP + TO ALARM SYSTEM CONTROL PANEL POLLING LOOP - POLLING LOOP TERMINALS. THIS DEVICE COMPLIES WITH PART 15 CLASS A ZONE A (DSM) LIMITS OF FCC RULES. OPERATION IS SUBJECT ZONE B (RTE) TO THE FOLLOWING TWO CONDITIONS: (1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
Page 50
The 4286 VIP Module features: Allows the user to receive synthesized voice messages over the phone regarding the status of the security system. • Allows the user to arm and disarm the security system and perform most other commands using the telephone •...
Serial Port Configuration The enhanced serial port on the Vista-32FBPT operates at a speed of 9600bps. Earlier Vista-32FB panels used a speed of 1200bps. (Please note that 1200bps option has been deleted and is no longer supported on Vista-32FBPT.) Depending on your application, you may need to adjust the configuration of your printer, home automation system or external software package to match the new faster speed.
Action Remove the front cover of the enclosure. Mount the enclosure to the wall near the VISTA-32FBPT control panel. The enclosure has four mounting holes on its back surface for this purpose. Run 120VAC wiring to the enclosure in conduit. A dedicated circuit must be used.
Determining the Control’s Power Supply Load In the event of an AC power loss the VISTA-32FBPT and the Commercial Fire Listed 24VDC Power Supply must be supported by backup, rechargeable batteries. When the system is used without a Commercial Fire Listed 24VDC Power Supply, a 12VDC, 12AH to 34.4AH battery must be connected the control panel.
Page 54
In Worksheet 1, enter devices used on the polling loop. Calculate total current draw on the polling loop. Worksheet 1: Total Polling Loop Current Draw Polling Loop Device Current # of Units Total Polling Loop Subtotal (terminals 28 & 29 – 128mA) * *The total current cannot exceed 128mA.
Page 55
In Worksheet 3, enter devices used on Auxiliary Power 2. Calculate standby and alarm currents, then add to get Auxiliary Power 2 current subtotal. Worksheet 3: Auxiliary Power 2 Current Load Total Current Device Device Current X Standby Alarm Model # # of Units Auxiliary Power 2 Subtotal (pin 5 on keypad port 2)
Page 56
(terminals 5 & 6 – 1.7A max.) 6. In Worksheet 6, enter the total calculated subtotals of all listed outputs from Worksheets 1 through 5, then add to get the combined current. Worksheet 6: Total VISTA-32FBPT Current Load Total Current Standby...
The standby battery is automatically tested for 10 minutes every 4 hours, beginning 4 hours after exiting Programming mode. In addition, entry into the Test mode initiates a battery test. The VISTA-32FBPT also runs a 5-second battery test every 60 seconds to check if the battery is connected.
NOTE: WHEN CONNECTING BATTERIES IN PARALLEL: BATTERY TABS USE THE 2nd PAIR OF BATTERY - USE BATTERIES FROM THE SAME MANUFACTURER AND TABS AND THE 2nd PAIR OF WITH THE SAME VOLTAGE AND CAPACITY RATING. BATTERY HARNESSES (NOT - USE BATTERIES WITH APPROXIMATELY SAME AGE AND SUPPLIED) TO CONNECT ONE STATE OF CHARGE.
Downloading allows the operator to remotely access, program, and control the security system over normal telephone lines, IP, or GSM Communicators. Anything that can be done directly from the keypad can be done remotely, using Honeywell’s COMPASS downloading software. To communicate with the control panel, the following is required. System Attributes...
Operator access levels: Operators may be assigned various levels of access to the downloader, each having its own log-on code. The access levels allow the operators read/write capabilities of the customers’ account information. For a detailed explanation of the access levels, see the downloading software User Manual. NOTES: Each time the control panel is accessed successfully, a Callback Requested report is sent to the central station, if •...
• Direct-Wire Downloading The VISTA-32FBPT can be downloaded without using a modem or telephone line. The direct-wire downloading connection is to be temporary, and is not part of the permanent installation. Direct-wire downloading is meant as a tool for the installer during the installation process.
Section 5: Setting the Real-Time Clock • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Information This system provides a real-time clock, which must be set in order for the system’s event log to keep track of events by time and date.
General Information The VISTA-32FBPT allows a total of 75 security access codes to be allocated. Each security access code is identified by a user ID number. Regardless of the number of partitions each code has access to, it occupies only one user slot in the system.
Levels 3-5: Operator Codes Can operate a partition, but cannot add or modify any user code (see table below). • Level Title Functions Permitted Operator A Arm, Disarm, Bypass Burg Zones Operator B Arm, Disarm Operator C Arm, Disarm only if armed with same code Operator C (sometimes known as the Babysitter Code) cannot disarm the system unless the system was armed with •...
The control automatically assigns him the same user number within Partition 2. EXAMPLE OF MULTIPLE PARTITION ACCESS Part 1 Part 2 User 3 User 3 Level 1 Level 4 Master Oper B In the above example, User 03 has MASTER authority in Partition 1 and OPERATOR B authority in Partition 2. His user number is the same for both partitions.
Press 0 (NO) or 1 (YES), depending on whether this user will be allowed to arm more than one Global Arm ? partition via Global Arm prompts (described in the VISTA-32FBPT User Guide). 0 = NO , 1 = YES The keypad now prompts for the user’s access to the next partition.
Battery Test When AC power is present, the VISTA-32FBPT runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery test every 4 hours to check on the battery’s condition.
For true detector sensitivity tests, and for compliance with fire codes, you must enter 0 (NO) to this question. PROMPT EXPLANATION Enter 1 (YES) to have the system log each point as it is tested. A list of untested points will also be logged. LOG RESULTS? Enter 0 (NO) if you do not want to log the results.
Armed Burglary System Test Alarm messages are sent to the central station during the armed tests. Notify the central station that a test will • be in progress. A display of “COMM FAILURE” indicates a failure to communicate (no kissoff by the receiver at the central •...
To enter the Go/No Go Test Mode, proceed as follows: Step Action Enter Installer Code + [5]. Fault each wireless transmitter, causing each device to transmit. The keypad will beep three times if the signal is received. If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in either direction is all that is required.
Display Description LSENS Indicates a smoke detector with a low sensitivity level. The detector may not detect a smoke condition. The detector should be cleaned or replaced. RCVR Indicates the system has more wireless zones programmed than the RF receiver can support. If this is not SETUP corrected, none of the zones in the system will be protected.
Page 74
Note the proper model number of this product, and the version level (if known) along with any documentation that • came with the product. Note your Honeywell customer number and/or company name. • Having this information handy will make it easier for us to serve you quickly and effectively.
The Vista-32FBPT has not been evaluated for use as a Slave Communicator in UL installations. Wiring Wire the Vista-32FBPT as shown in Figure 8-1 below. Be sure to tag the wires at the Terminal Box to identify their connections between the Fire Alarm Panel and the Vista-32FBPT.
Fire Alarm Control for local annunciation at the Fire System Operator Interface. To do this, connect a 4204CF relay to the VISTA-32FBPT and wire the relay outputs to input zones at the Fire Alarm panel as shown below.
The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the cabinet door (supplied with VISTA-32FBPT). Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for multiple partitioned systems.
Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds. All unused knockouts must be plugged (use the supplied disc plugs and carriage bolts). Must be used with a Listed burglar alarm sounding device/housing. Depending on the application, a compatible Listed sounding device enclosure may also be required.
Page 79
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. FCC CLASS B STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
Page 80
CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE AVIS L’étiquette d’Industrie Canada identifie The Industry Canada Label identifies certified equipment. This certification means that the matériel homologué. Cette étiquette certifie que le equipment meets telecommunications network matériel est conforme aux normes de protection, protective, operational and safety requirements as d’exploitation et de sécurité...
MX8000 5140DLM BACKUP DIALER MODULE Physical: 2.75”H X 4”W X 1”D Mounts on VISTA-32FBPT main PC board shield using standoffs supplied. Connects to VISTA-32FBPT main PC board J3 header using ribbon cable supplied. FCC Registration: AC3-USA-62628-MO-N UL/ULC Listings: Standard. No.
Code Definition NOTE: If there is a phone line (or radio) failure and the Burglary Walk-Test panel has exhausted its maximum attempts to send reporting events to the central station, the panel will Off-Normal hold the messages in a buffer and resend upon restoral Fire Walk-Test –...
Page 87
Alpha Event Description Alpha Event Description RFLB RST RF Low Battery Restore EXITED Egress Granted EXP RST Expansion Module Failure Restore ACLO MOD AC Loss at Module TMPR RST Tamper Restore LBAT MOD Low Battery at Module FRTR RST Fire Trouble Restore COMM MOD Comm Failure from MLB to Module COMM RESTORE...
Page 90
Factory defaults can be loaded at anytime by hitting *97 in the panels program mode. • Fixed Word: All Honeywell keypads use English language displays; some keypads (“alpha”) are capable of fully programmable alpha-numeric description for each zone; other keypads are non-alpha programmable but uses Fixed Glass words on the display, such as Ready, Not ready, Armed, Disarmed, etc.
Page 91
• Hardwire Expansion: The ability to add additional hardwire zones to some controls by adding a hardwire expansion module • Heat Detector (Heat Stat): A device that activates when the ambient temperature reaches 135 degrees (or 190); other types measure quick rises in temperature (“rate of rise”) •...
Page 92
• PIR: Abbreviation for Passive Infra red motion detector • Partition: An area within a total system that can be separately controlled as if it were an individual system. • Partition Descriptor: A 4-character name that can be programmed in some controls to identify each partition. •...
Page 93
• Upload: To get the program data over the phone line, IP connection, etc. from the control panel to the computer • User Code: a.k.a. Access code, Security Code; Always 4-digits • V.I.P.: Abbreviation for Voice interactive Phone Module (4286) • Vista: A line of Honeywell Panels • Wireless: a.k.a. RF; Refers to the 5800/5700 series wireless transmitters and receivers •...
Page 96
Partitioned System ..........17 Partitioning ............13, 17 Hardwire and Optional Expansion Zones ....11 Peripherals Devices ..........12 Honeywell 4146 ............43 Phone Module Access Code ........7 PLL out of Lock ............46 Polling Loop ............35 Polling Loop Current Draw ........53 Installer (User 1) Code Level 0 .......
Page 97
View Capabilities............ 65 System Communication .......... 13 VIP Module ............48 SYSTEM LO BAT ........... 74 VISTA-32FBPT Current Load ........ 55 System LoBat” ............71 VistaKey ..............46 System Messages ..........74 System Sensor EOLR-1 EOL Relay Module ..34 Wire Run Length/Gauge ........
Page 98
THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a vari- ety of reasons.
Page 99
For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa...
Page 102
Vista-32FBPT Commercial/Residential Fire and Burglary, Mercantile/Bank Safe and Vault, Local and Police Station, Central Station and Proprietary Protected Premises Control Unit with DACT Applications Wiring Diagram...
Page 103
Vista-32FBPT Commercial/Residential Fire, Household Burglary and Protected Premises Control Unit Applications Wiring Diagram...