Honeywell ademco vista-48la Programming Manual
Honeywell ademco vista-48la Programming Manual

Honeywell ademco vista-48la Programming Manual

Hide thumbs Also See for ademco vista-48la:

Advertisement

ADEMCO VISTA-48LA

Security System

Programming Guide
K0749-6ENPR
5/05 Rev. A

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ademco vista-48la

  • Page 1: Security System

    ADEMCO VISTA-48LA Security System Programming Guide K0749-6ENPR 5/05 Rev. A...
  • Page 2: To Exit Programming Mode

    FIRST STEP: SELECT THE LANGUAGE When programming the system, you should first select the appropriate language by doing the following: 1. Enter Programming mode. 2. Press [∗] + 28 (Language Select data field). 3. Press the number corresponding to the desired language: 0 = English, 1 = Spanish, 2 = Portuguese 4.
  • Page 3: Installer Code

    PR O G R AM M IN G F O R M Entry of a number other than one specified will give unpredictable results. Default values are shown in brackets, with unique table 1 and table 2 values indicated where applicable (fields *28 and *35; DT1 = default table 1; DT2 = default table 2). ∗20 ∗...
  • Page 4: Bypass Report Code

    ∗ ∗ ∗ ∗ 43 ∗ ∗ ∗ ∗ 61 Primary Subscriber ID # (Part.1) Bypass Report Code ∗ ∗ ∗ ∗ 62 AC Loss Report Code ∗ ∗ ∗ ∗ 44 Secondary Subscriber ID # (Part.1) ∗ ∗ ∗ ∗ 63 Low Bat Report Code ∗...
  • Page 5 ∗ ∗ ∗ ∗ 165 ∗ ∗ ∗ ∗ 88 Pager 2 Reporting Options Exit Options 0 = all intrusion zones must be intact before arming (must be 0 if [0,0,0] See field *162 for entries. Part. 1 Part. 2 Part 3 system uses zone type 82 - Blockschloss) Use zone list 10 if using options 12 or 13.
  • Page 6: Keypad Options

    KEYPAD OPTIONS ∗ ∗ ∗ ∗ 182 Summer Time Switchover Day NOTES: 1. Keypad 1 (addr 16) options are factory set and cannot be changed. 2. Each keypad must be assigned a unique address. Keypads 0 = switch on Sunday morning; 1= switch on Saturday morning programmed with the same address will give unpredictable results.
  • Page 7 *56 ZONE PROGRAMMING WORKSHEET [default values shown in brackets] Zone Zn Type Partition Report Basic Wired Type Response Time Location [01] [EOL] [04] [EOL] [03] [EOL] [03] [EOL] [03] [EOL] [03] [EOL] [03] [EOL] [03] [EOL] Zone Zn Type Partition Report Input Type Loop...
  • Page 8: Input Type

    ∗ ∗ ∗ ∗ 56 ZONE PROGRAMMING MENU MODE (press *56 while in Program mode) 0 = no SET TO CONFIRM? 1 = yes (prompt appears after entering the serial and loop numbers to confirm each transmitter) 0 = NO 1 = YES We recommend that you confirm the programming of every transmitter.
  • Page 9 If the serial/loop number combination is not a duplicate in the system, a display showing the serial number 10 INPUT S/N and loop number entry appears. A 0 2 2 - 4 0 6 4 [∗] to continue This prompt will only appear if you answered “Yes” at the first prompt in this section. XMIT TO CONFIRM The system will enter a confirmation mode so that the operation of the actual programmed input can be ✱...
  • Page 10 Wireless Key Programming Templates (press the [D] key from *58 Menu mode Summary Screen display) This procedure programs the wireless keys, but a key is not active until it is assigned to a user number (see System Operation section, assigning attributes command in the Installation Instructions). Enter desired template number 1–6 (see chart below).
  • Page 11: Table Of Device Addresses

    Table of Device Addresses Report † Device Address Programmed by… RF Receiver *56 zone programming: input device type entry; Alternative Communication Media (ACM) automatic if ECP Contact ID Output for ACM field *29 enabled 17-23 117-123 Telecommand Voice Module same as keypad enables; see below Zone Expanders (4219/4229)/6164 Keypad: *56 zone programming: input device type entry, then: •...
  • Page 12 OUTPUT RELAYS/POWERLINE CARRIER DEVICES WORKSHEET FOR ∗ ∗ ∗ ∗ 79, ∗ ∗ ∗ ∗ 80 and ∗ ∗ ∗ ∗ 81. For keypad activated devices, use *79 Menu mode to assign a system output number and associate its corresponding device. For automatic activation, use *79 Menu mode as above, and use *80 Menu mode to define the system condition that will activate/deactivate the device(s).
  • Page 13 ✱ OUTPUT DEFINITIONS NOTES: 1. For Relays, 4229, 4204, and 6164 devices are programmed in *79, *80, and *81 modes. ✱ 2. For Powerline Carrier devices (plcd), field 27 must be programmed with a House Code. 3. Tampers of expansion units cannot be used to operate devices. Zone Types: 00 = Not used 07 = 24-Hr Audible...
  • Page 14 Start Output Definition mode by pressing ∗ ∗ ∗ ∗ 80 while in Data Programming mode. Enter the output function number to be defined Output Funct. # 01-48 = output function number (00 = Quit) [∗] to continue 00 = exit This screen displays a summary of the current output programming A E P Trig A = Output Action;...
  • Page 15: Zone Lists

    ✱ 81 ZONE LISTS List No. Used For… Contains These Zones… General Purpose (GP) General Purpose Chime-by-Zone or GP Linked Zones Night-Stay Zones or GP General Purpose General Purpose Final Contact Set Zones or G P Zones activating pager 1 or G P Zones activating pager 2 or G P General Purpose Exit Zones (*88) or GP...
  • Page 16 DESCRIPTOR PROGRAMMING Start Zone Descriptor Programming mode by pressing *82 while in Data Programming mode. The “Program Alpha ?” prompt appears. P r o g r a m A l p h a ? 1 = program zone descriptors, partition descriptors, or reminder words 0 = exit 0 = N o , 1 = Y e s 0 0 [∗] to continue...
  • Page 17: Alarm Sound

    CONFIGURABLE ZONE TYPE PROGRAMMING CONFIGURABLE ZONE TYPE WORKSHEET Option ZT 90 ZT 91 ZT 92 ZT 93 Option Selections Zone Attributes Zone Attributes Vent Zone Sound on Alarm 0 = none 0=no; 1=yes 0=none Bypass Option 1 = exit delay only 1= keypad sound only Response to Short Zone Processing...
  • Page 18 Schedules installer code + [#] + [6] [4]; master code can only access schedules 01-24 and events 00-08 ) Sched Event Device No. User Partition Start Time/ Days Warning Stop Time/ Days Repeat Random Group Delay (see list for event for events select days by select days by...
  • Page 19 This prompt appears if event “1” (relay on/off) was selected, otherwise it is skipped. D E V I C E N U M B E R Enter the physical device number as programmed in ∗79 Menu Mode, then press [*] to continue to the “Start” prompt.
  • Page 20 – NOTES – – 20 –...
  • Page 21 – NOTES – – 21 –...
  • Page 22 WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: •...
  • Page 23: Limited Warranty

    Honeywell factory service. Connection of any device(s) to a communicating bus of a Honeywell security system (e.g., keypad bus, polling loop) other than those manufactured or approved by Honeywell shall void this warranty. For warranty service, return...
  • Page 24 165 Eileen Way, Syosset, NY 11791 Copyright © 2005 Honeywell International Inc. www.honeywell.com/security ÊK0749-6ENPRXŠ K0749-6ENPR 5/05 Rev. A...

Table of Contents