Shipping And Packing List; General; Unit Support - Lennox LCH036 Installation Instructions Manual

Table of Contents

Advertisement

Shipping and Packing List

Package 1 of 1 contains:
1- Assembled unit
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.
IMPORTANT - Hot gas reheat units require a specific
field-provided and installed humidity sensor or digital
input. Refer to control wiring section.

General

These instructions are intended as a general guide and do
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.
Use of this unit as a construction heater or air conditioner is
not recommended during any phase of construction. Very
low return air temperatures, harmful vapors and operation
of the unit with clogged or misplaced filters will damage the
unit.
If this unit has been used for heating or cooling of buildings
or structures under construction, the following conditions
must be met or the warranty will be void:
S The vent hood must be installed per these installation
instructions.
S A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or
cooling is not allowed.
S A pre-filter must be installed at the entry to the return air
duct.
S The return air duct must be provided and sealed to the
unit.
S Return air temperature range between 55°F (13°C) and
80°F (27°C) must be maintained.
S Air filters must be replaced and pre-filters must be
removed upon construction completion.
S The input rate and temperature rise must be set per the
unit rating plate.
S The heat exchanger, components, duct system, air
filters and evaporator coil must be thoroughly cleaned
following final construction clean-up.
S The unit operating conditions (including airflow, cooling
operation, ignition, input rate, temperature rise and
venting) must be verified according to these installation
instructions.
507232-02
9/2015
Requirements
See figure 1 for unit clearances.
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFC's and HCFC's) as of July 1, 1992.
Approved methods of recovery, recycling or reclaim­
ing must be followed. Fines and/or incarceration may
be levied for non-compliance.
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to swell. Bubbles in the rubber roofing
material can cause leaks. Protect the roof surface to
avoid exposure to refrigerant and oil during service
and installation. Failure to follow this notice could
result in damage to roof surface.

Unit Support

Danger of sharp metallic edges. Can cause injury.
Take care and wear protective clothing when
servicing unit to avoid accidental contact with sharp
edges.
In downflow discharge installations, install the unit on a
non-combustible surface only. Unit may be installed on
combustible surfaces when used in downflow discharge
applications when installed on an S1CURB10E-1 roof
mounting frame.
NOTE - Securely fasten roof frame to roof per local codes.
To reduce the likelihood of supply / return air bypass
and promote a proper seal with the RTU, duct work /
duct drops / diffuser assemblies must be supported
independently to the building structure.
Page 5
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing
any
maintenance
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
IMPORTANT
NOTICE
CAUTION
CAUTION
or