Shipping And Packing List; General - Lennox LGT156H Installation Instructions Manual

Table of Contents

Advertisement

Shipping and Packing List

Package 1 of 1 contains:
1- Assembled unit
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is found.

General

These instructions are intended as a general guide and
do not supersede local codes in any way. Authorities
having
jurisdiction
should
installation.
The LGT156H gas/electric packaged rooftop unit is
available in 169, 000, 260,000, & 360,000 Btuh heating
input. The LGT180, 210, 240, & 300 gas/electric
packaged rooftop units are available in 260,000,
360,000, or 480,000 Btuh heating inputs.
The LCT cooling packaged rooftop unit is the same basic
design as the LGT unit except for the heating section.
Optional electric heat is factory- or field-installed in LCT
units.
LGT and LCT units have identical refrigerant circuits with
respective 13, 15, 17‐1/2, 20 and 25 ton cooling
capacities. 156H units contain two compressors;
compressor 1 is two speed and compressor 2 is fixed
speed. 180H units contain three compressors; all are
fixed speed. 210, 240 and 300 units contain four
compressors; all are fixed speed compressors.
Units come standard with a factory-installed, all-aluminum
condenser coil.
Units are available with an optional hot gas reheat coil
which provides a dehumidifying mode of operation. Refer
to Reheat Operation section.
Units are available with variable air volume or single-zone
variable air volume. Refer to the 9
model number to determine type of blower:
V - Variable Air Volume
M - Single-Zone Variable Air Volume
Units use R410A, an ozone-friendly HFC refrigerant.
Refer to the Cooling Start-Up section for precautions
when installing unit.
LGT/LCT156, 180, 210, 240, 300
be
consulted
before
th
character of the
Page 6
WARNING
Electric shock hazard and danger of
explosion. Can cause injury, death or
product or property damage. Turn off
gas and electrical power to unit before
performing
servicing operations on the unit. Follow
lighting instructions attached to unit
when putting unit back into operation
and after service or maintenance.
Requirements
See figure 1 for unit clearances.
UNIT CLEARANCES
Optional
Outdoor
Air Hood
D
A
FIGURE 1
1 Unit
A
B
in.(mm)
in.(mm)
Clearance
Service
60
36
Clearance
(1524)
(914)
Clearance to
36
Combus­
1 (25)
(914)
tibles
Minimum
36
36
Operation
(914)
(914)
Clearance
Note - Entire perimeter of unit base requires support when elevated above
mounting surface.
1 Service Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material
(gas units). On LCT units, see clearance to combustible materials outlined
on heater rating plate.
Minimum Operation Clearance - Required clearance for proper unit operation.
any
maintenance
C
B
C
D
Top
in.(mm)
in.(mm)
Clearance
36
66
Unob­
(914)
(1676)
structed
Unob­
1 (25)
1 (25)
structed
36
41
Unob­
(914)
(1041)
structed
or