Optional Outdoor Air CFM Control
Outdoor air CFM Control is a factory-installed option
available on units equipped with a supply air variable
frequency drive (VFD) and economizer.
The Unit Controller modulates outdoor air dampers to
maintain a constant amount of outdoor air regardless of
blower speed. This ensures minimum ventilation
requirements are met at lower supply air speeds.
The Unit Controller uses a velocity sensor (A24) to
modulate dampers. The sensor is located in the outdoor
air stream. See figure 34.
Set Damper Minimum Position
1- Operate unit at full supply air CFM with all zone
dampers open. Refer to VFD Supply Air Blower
Start-Up section in this manual.
2- Use an air flow hood to measure the outdoor air CFM
entering the unit.
3- Set economizer DIP switch to "DSET" position as
shown in figure 36. DIP switch is located on the A55
Unit Controller board. See figure 35.
4- Adjust the MIN POS SET potentiometer until the air
flow hood reads the design minimum outdoor air
CFM. See figure 36.
LED FLASHING GREEN
"HEARTBEAT" LED
INDICATES NORMAL
OPERATION
B
C
D
IN "ODE" MODE, SET ENTHALPY
CONTROL IN "A" POSITION. IF AIR
IS TOO HUMID, ROTATE CLOCK
A
DIF
ENTHALPY
WISE TO LOWER SETTING
SETPOINT
NOTE - Refer to local codes or authorities having
jurisdiction when determining design minimum outdoor
air requirements.
5- Return the economizer DIP switch to original
position. Refer to the Unit Controller manual.
ECONOMIZER SETTINGS
STEADY YELLOW "OUT
DOOR AIR SUITABLE" LED
INDICATES OUTDOOR AIR IS
SUITABLE FOR COOLING
TMP GLO
GLO TMP
C
OPEN
D
B
A
0
100
DIF
ENTH. SET PT.
MIN POS SET
0-100% MINIMUM
POSITION POTEN
TIOMETER
FIGURE 35
Page 40
VELOCITY SENSOR LOCATION
FIGURE 34
A FLASHING YELLOW
OAS LED INDICATES THE
IAQ SENSOR IS REQUEST
ING MORE FRESH AIR
DIP SWITCH SET
IN TMP, ODE, DIF
OR GLO MODE
OPEN
0
100
MIN POS
SET
A24
SENSOR
A24
CONTROL