Factory Unit Controller Settings
Use the Unit Controller to adjust parameters; menu paths
are shown in each table. Refer to the Unit Controller
manual provided with each unit.
Tables 33 through 36 show factory settings (in degrees, %
of fan CFM, etc.). Record adjusted settings on the label
located inside the compressor access panel.
When field installing optional kits and accessories, the
Unit Controller must be configured to identify the option
before it will function. Refer to figures 36 and 37 to
determine whether the Unit Controller configuration I.D.
must change. To configure the option, use MAIN MENU >
SETUP > INSTALL menu path. Press SAVE until
CONFIGURATION ID 1 or 2 appears depending on the
option installed. Change the appropriate character in the
configuration I.D. For example, when an economizer is
installed using a single enthalpy sensor, change
configuration I.D. 1, the second character, to "S".
TABLE 33
580730
Units With BACnet Module Settings
Use menu SETUP > NETWORK INTEGRATION. Set "BACNET" and
network address.
BACNET MAC ADDRESS:
TABLE 34
580732
Units With Room Sensor, CPC/LSE Gateway Settings
Use menu SETUP > NETWORK INTEGRATION. Set "L CONNEC­
TION" and network address.
LCONN ADDRESS:
Units With Hot Gas Reheat
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
Para­
Factory
Field
meter
Setting
Setting
105
6
Units with BACnet Module (Target) Settings
Use menu SETUP > NETWORK INTEGRATION. Set "BACNET"
and network address.
BACNET MAC ADDRESS:
Para­
Factory
meter
Setting
Setting
Use SETTINGS > RTU OPTIONS > EDIT PARAMETERS
91
120
106
99
111
3
117
0
153
60
Page 48
TABLE 35
580734
Description
Hot Gas Reheat Option 6: Reheat is
only possible if blower is energized dur­
ing occupied periods. Controlled by RH
sensor (A91) connected to input
A55_P298_5 and set point set at para­
meter 106 (default 60%).
TABLE 36
580735
Description
Sets the compressor minimum run
time to 2 minutes.
Set reheat SP from connected sensor
to 99% to basically disable. Reheat
will be controlled over by BAS. Only
applies to units with the reheat option.
Thermostat with three cooling stages.
DCV max. open damper. 0=controlled
by network.
Time delay between heating and cool­
ing mode.
LGH/LCH036, 048, 060, 072