Lennox LCH036 Installation Instructions Manual page 79

Table of Contents

Advertisement

TABLE 14
LGH/LCH120H Fin/Tube - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+10 psig
+5 psig
Air Temp
655 F
259
755 F
297
855 F
338
955 F
382
1055 F
431
1155 F
486
TABLE 15
LGH/LCH120H Fin/Tube Hot Gas Reheat - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
charge
Suction
Entering
+5 psig
+10 psig
Air Temp
655 F
266
755 F
303
855 F
344
955 F
391
1055 F
443
1155 F
499
TABLE 16
LGH/LCH150S Fin/Tube Hot Gas Reheat - TXV
CIRCUIT 1
Outdoor
Dis­
Coil
Suction
charge
Entering
+10 psig
+5 psig
Air Temp
655 F
280
755 F
319
855 F
360
955 F
407
1055 F
455
1155 F
510
CIRCUIT 2
Dis­
Suction
charge
+10 psig
+5 psig
137
283
139
140
321
142
143
360
144
146
406
146
149
453
148
151
505
151
CIRCUIT 2
Dis­
charge
Suction
+5 psig
+10 psig
134
281
139
137
310
141
140
358
143
143
403
145
146
450
146
149
497
148
CIRCUIT 2
Dis­
Suction
charge
+10 psig
+5 psig
136
296
136
141
335
141
142
376
143
144
420
144
147
466
147
150
518
150
Charge Verification - Approach Method - AHRI Testing
(Fin/Tube Coil Continued)
1- Using the same thermometer, compare liquid
temperature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
condenser outlet) minus ambient temperature.
2- Approach temperature should match values in table
17. An approach temperature greater than value
shown indicates an undercharge. An approach
temperature less than value shown indicates an
overcharge.
3- The approach method is not valid for grossly over or
undercharged systems. Use tables 10 through 16 as
a guide for typical operating pressures.
APPROACH TEMPERATURE - Fin/Tube - TXV
Unit
092
6°F + 1 (3.3°C + 0.5)
102
6°F + 1 (3.3°C + 0.5)
120
6°F + 1 (3.3°C + 0.5)
092 Reheat
120 Reheat
6°F + 1 (3.3°C + 0.5)
150 Reheat
102 Reheat
6°F + 1 (3.3°C + 0.5)
Page 29
TABLE 17
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
7°F + 1 (3.9°C + 0.5)
9°F + 1 (5.0°C + 0.5)
10°F + 1 (5.6°C + 0.5)
8°F + 1 (4.4°C + 0.5)
9°F + 1 (5.0°C + 0.5)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lgh036Lgh048Lgh060Lgh072Lch048Lch060 ... Show all

Table of Contents