G-Condenser Coil
All-Aluminum Coils -
Clean condenser coil annually with water and inspect
monthly during the cooling season.
Clean the all-aluminum coil by spraying the coil steadily
and uniformly from top to bottom. Do not exceed 900 psi
or a 45_ angle; nozzle must be at least 12 inches from the
coil face. Take care not to fracture the braze between the
fins and refrigerant tubes. Reduce pressure and work
cautiously to prevent damage.
TOP VIEW
SUPPLY
AIR
BLOWER
CONDENSER ACCESS PANEL
LGH/LCH036, 048, 060, 072
CLEAN CONDENSER COIL - UNITS WITH FIN/TUBE COILS
ENDPLATE IS SECURED
TO MULLION
CONDENSER
Fin/Tube Coils -
Clean condenser coil annually with detergent or
commercial coil cleaner and inspect monthly during the
cooling season.
Condenser coils are made of single and two formed slabs.
On units with two slabs, dirt and debris may become
trapped between the slabs. To clean between slabs,
carefully separate coil slabs and wash them thoroughly.
See figure 35. Flush coils with water following cleaning.
Note - Remove all screws and gaskets prior to cleaning
procedure and replace upon completion.
H-Supply Air Blower Wheel
Annually inspect supply air blower wheel for accumulated
dirt or dust. Turn off power before attempting to remove
access panel or to clean blower wheel.
1-
Remove unit top panel and condenser section access
panel.
2-
Remove screws securing coil end plate to mullion.
3-
Remove wire ties connecting coils slabs and separate
slabs 3-4" (76-102mm).
4-
Clean coils with detergent or commercial coil cleaner.
5-
Rinse thoroughly with water and reassemble
field-provided wire ties to connect coil slabs.
COILS
FIGURE 35
Page 47
.