D-Refrigerant Charge and Check
WARNING-Do not exceed nameplate charge under any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add required
nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in cooling mode. Make sure hot
gas reheat is not energized.
1- Attach gauge manifolds and operate unit in cooling
mode at full CFM with economizer disabled until system
stabilizes (approximately five minutes). Make sure all
outdoor air dampers are closed.
2- Check each system separately with all stages operating.
3- Use a thermometer to accurately measure the outdoor
ambient temperature.
4- Apply the outdoor temperature to tables 7 through 18 to
determine normal operating pressures. Pressures are
listed for sea level applications at 80°F dry bulb and
67°F wet bulb return air.
5- Compare the normal operating pressures to the
pressures obtained from the gauges. Minor variations
in these pressures may be expected due to differences
in installations. Significant differences could mean that
the system is not properly charged or that a problem
exists with some component in the system. Correct
any system problems before proceeding.
6- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add refrigerant
to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time
refrigerant is added or removed.
7- Use the following approach method along with the
normal operating pressures to confirm readings.
LGH/LCH420S - R410A - CAV
Circuit 1
Circuit 2
Outdoor
Coil En­
Dis.
Suc.
Dis.
tering Air
+10
+5
+10
Temp
psig
psig
psig
65_F*
270
131
317
75_F
313
134
341
85_F
355
136
391
95_F
396
138
446
105_F
446
140
500
115_F
500
142
552
TABLE 7
Circuit 3
Circuit 4
Suc.
Dis.
Suc.
Dis.
+5
+10
+5
+10
psig
psig
psig
psig
136
291
134
291
139
331
137
331
142
375
138
370
144
418
140
412
147
464
141
452
150
513
142
507
Circuit 1
Outdoor
Coil En­
Dis.
tering Air
+10
Temp
psig
65_F*
280
75_F
330
85_F
380
95_F
420
105_F
495
115_F
535
Circuit 1
Outdoor
Coil En­
DIs
tering Air
+10
Temp
psig
65_F*
230
75_F
290
85_F
320
95_F
390
105_F
440
115_F
500
Circuit 1
Outdoor
Coil En­
DIs
tering Air
+10
Temp
psig
65_F*
250
75_F
300
85_F
330
95_F
390
105_F
420
115_F
470
Circuit 1
Outdoor
Coil En­
DIs
tering Air
+10
Temp
psig
65_F*
270
75_F
313
85_F
355
95_F
396
105_F
446
115_F
500
Circuit 1
Outdoor
Coil En­
DIs
Suc.
tering Air
+10
+5
Temp
psig
psig
65_F*
282
133
75_F
336
134
85_F
389
137
95_F
429
139
105_F
502
141
143
115_F
547
Page 32
TABLE 8
LGH/LCH420S - R410A - VFD
Circuit 2
Circuit 3
Suc.
Dis.
Suc.
Dis.
+5
+10
+5
+10
psig
psig
psig
psig
112
310
115
310
115
360
118
350
117
410
121
400
121
470
125
450
124
530
128
510
128
590
131
570
TABLE 9
LGH/LCH420H - R410 - CAV
Circuit 2
Circuit 3
Suc
Dis
Suc
DIs
+5
+10
+5
+10
psig
psig
psig
psig
127
300
133
260
134
330
135
300
135
380
137
340
137
430
139
390
143
490
142
440
146
550
144
500
TABLE 10
LGH/LCH420H - R410 - VFD
Circuit 2
Circuit 3
Suc
Dis
Suc
DIs
+5
+10
+5
+10
psig
psig
psig
psig
121
280
124
260
124
320
126
305
126
370
127
340
130
420
131
400
131
470
132
450
134
540
134
510
TABLE 11
LGH/LCH480S - R410A - CAV
Circuit 2
Circuit 3
Suc
Dis
Suc
DIs
+5
+10
+5
+10
psig
psig
psig
psig
131
317
136
291
134
341
139
331
136
391
142
375
138
446
144
418
140
500
147
464
142
552
150
513
TABLE 12
LGH/LCH480S - R410A - VFD
Circuit 2
Circuit 3
Suc
Dis
Suc
DIs
+5
+10
+5
+10
psig
psig
psig
psig
114
317
116
315
116
361
118
353
119
414
121
403
122
470
124
451
126
529
128
511
130
595
131
576
LGH/LCH420, 480, 540, 600
Circuit 4
Suc.
Dis.
Suc.
+5
+10
+5
psig
psig
psig
137
312
141
140
350
143
142
380
141
144
435
143
146
490
147
148
550
150
Circuit 4
Suc
DIs
Suc
+5
+10
+5
psig
psig
psig
130
270
130
132
300
131
135
340
132
136
370
133
139
430
137
141
490
139
Circuit 4
Suc
DIs
Suc
+5
+10
+5
psig
psig
psig
140
270
140
142
306
142
143
350
144
146
390
147
147
460
148
149
520
150
Circuit 4
Suc
DIs
Suc
+5
+10
+5
psig
psig
psig
134
291
133
137
331
134
138
370
137
140
412
139
141
452
141
142
507
143
Circuit 4
Suc
DIs
Suc
+5
+10
+5
psig
psig
psig
138
316
139
139
351
143
142
396
145
144
441
144
147
498
147
149
558
150