C-Refrigerant Charge and Check - All-Aluminum Coil
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add
required nameplate charge.
NOTE - System charging is not recommended below
60_F (15_C). In temperatures below 60_F (15_C), the
charge must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode
high stage only.
1- Make sure outdoor coil is clean. Attach gauge
manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.
2- Compare the normal operating pressures (see tables
7 - 13) to the pressures obtained from the gauges.
Check unit components if there are significant
differences.
3- Measure the outdoor ambient temperature and the
suction pressure. Refer to the appropriate circuit
LGH/LCH036S NORMAL OPERATING PRESSURES - ALL-ALUMINUM COIL
65 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
113
235
117
121
239
122
138
248
141
157
264
160
LGH/LCH036H NORMAL OPERATING PRESSURES - ALL-ALUMINUM COIL
65 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
115
242
116
121
245
124
138
255
143
155
267
160
LGH/LCH036, 048, 060, 072
Outdoor Coil Entering Air Temperature
75 F
85 F
Disc
Suct
(psig)
(psig)
(psig)
274
116
284
125
288
144
297
163
Outdoor Coil Entering Air Temperature
75 F
85 F
Disc
Suct
(psig)
(psig)
(psig)
283
119
284
126
294
146
305
165
charging curve to determine a target liquid
temperature.
Note - Pressures are listed for sea level applications.
4- Use the same thermometer to accurately measure the
liquid temperature (in the outdoor section).
D If measured liquid temperature is higher than
the target liquid temperature, add refrigerant to
the system.
D If measured liquid temperature is lower than
the target liquid temperature, recover some
refrigerant from the system.
5- Add or remove charge in increments. Allow the
system to stabilize each time refrigerant is added or
removed.
6- Continue
temperature
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
7- Example LGH/LCH036H: At 95°F outdoor ambient
and a measured suction pressure of 130psig, the
target liquid temperature is 98°F. For a measured
liquid temperature of 106°F, add charge in
increments until measured liquid temperature agrees
with the target liquid temperature.
TABLE 7
95 F
Disc
Suct
Disc
(psig)
(psig)
329
118
379
327
127
378
329
147
375
339
167
387
TABLE 8
95 F
Disc
Suct
Disc
(psig)
(psig)
328
120
382
329
128
379
340
148
389
349
168
399
Page 29
the
process
until
measured
agrees
with
the
105 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
121
438
124
129
437
132
151
427
151
172
437
175
105 F
Suct
Disc
Suct
(psig)
(psig)
(psig)
122
444
124
129
447
131
151
441
152
171
454
175
liquid
target
liquid
115 F
Disc
(psig)
497
506
497
492
115 F
Disc
(psig)
535
528
515
514