Lennox LCH036 Installation Instructions Manual page 28

Table of Contents

Advertisement

Motor Pulley
Drive No.
Supplier No.
A01
1VP34x7/8
A02
1VP34x7/8
A03
1VP34x7/8
A05
1VP34x7/8
A06
1VP44x7/8
A07
1VP50x7/8
AA01
1VP34x7/8
AA02
1VP40x7/8
AA03
1VP40x7/8
AA04
1VP44x7/8
2
A01T
1VP34x7/8
2
A02T
1VP34x7/8
2
A03T
1VP34x7/8
2
A05T
1VP34x7/8
2
A06T
1VP44x7/8
2
A07T
1VP50x7/8
2
AA01T
1VP34x7/8
2
AA02T
1VP40x7/8
2
AA03T
1VP40x7/8
2
AA04T
1VP44x7/8
1
NOTES:
Requires split taper bushing, Browning no. H1; OEM no. 100073-04
Cooling Start-Up
A-Operation
1- Initiate first and second stage cooling demands
according to instructions provided with Unit
Controller Installation and Setup Guide. Use the
menu navigation arrows and select button; see
SERVICE > TEST
2- No Economizer Installed in Unit -
A first-stage cooling demand (Y1) will energize the
compressor and blower in low speed along with the
condenser fan. An increased cooling demand (Y2)
will increase the blower and compressor to high
speed.
Units Equipped With Economizer -
When outdoor air is acceptable, a first-stage
cooling demand (Y1) will energize the economizer.
An increased cooling demand (Y2) will energize
the compressor and low speed blower along with
the condenser fan. When outdoor air is not
acceptable unit will operate as though no
economizer is installed.
3- Units contain one refrigerant circuit or stage.
4- Unit is charged with R-410A refrigerant. See unit
rating plate for correct amount of charge.
MANUFACTURER'S DRIVE COMPONENT NUMBERS
OEM Part No.
Supplier No.
31K6901
AK54 x 1
31K6901
AK49 x 1
31K6901
AK44 x 1
31K6901
AK41 x 1
P-8-1488
AK51 x 1
P-8-2187
AK54 x 1
31K6901
AK69 x 1
1
79J0301
BK80H
79J0301
AK59 x 1
P-8-1488
AK59 x 1
31K6901
AK54 x 1
31K6901
AK49 x 1
31K6901
AK44 x 1
31K6901
AK41 x 1
P-8-1488
AK51 x 1
P-8-2187
AK54 x 1
31K6901
AK69 x 1
79J0301
BK80H*
79J0301
AK59 x 1
P-8-1488
AK59 x 1
TABLE 6
DRIVE COMPONENTS
Blower Pulley
OEM Part No.
100244-19
100244-18
100244-16
100244-15
18L2201
100244-19
37L4701
100788-03
31K6801
31K6801
100244-19
100244-18
100244-16
100244-15
18L2201
100244-19
37L4701
100788-03
31K6801
31K6801
2
Includes tension assembly, Fenner no. FS0590; OEM no. 101994-02
5- Refer to Cooling Operation and Adjustment section for
proper method to check refrigerant charge.
B-Three Phase Scroll Compressor Voltage Phasing
Three phase scroll compressors must be phased
sequentially to ensure correct compressor and blower
rotation and operation. Compressor and blower are
wired in phase at the factory. Power wires are
color-coded as follows: line 1-red, line 2-yellow, line
3-blue.
1- Observe suction and discharge pressures and
blower rotation on unit start-up.
2- Suction pressure must drop, discharge pressure
must rise, and blower rotation must match rotation
marking.
If pressure differential is not observed or blower rotation is
not correct:
3- Disconnect all remote electrical power supplies.
4- Reverse any two field-installed wires connected to
the line side of K1 contactor. Do not reverse wires at
blower contactor.
5- Make sure the connections are tight.
Discharge and suction pressures should operate at
their normal start‐up ranges.
Page 28
bELT
Supplier No.
OEM Part No.
A40
100245-17
A39
100245-16
A39
100245-16
A39
100245-16
A41
100245-18
AX43
73K8201
AX51
13H0101
A53
P-8-4951
A50
100245-29
AX51
13H0101
A41
100245-18
A40
100245-17
A40
100245-17
A41
100245-18
A41
100245-18
AX43
73K8201
A50
100245-29
A52
100245-30
A49
100245-32
A50
100245-29
LGH/LCH036, 048, 060, 072