10

UV Vessel Installation

Purpose
Proper installation of the UV Vessel achieves expected results and ensures safe operation.
Frequency
Required with new construction, retro-fit or replacement of outdated equipment.
Parts and Required Equipment
• Socket Wrenches
• Adjustable Wrenches
• Set of Slotted and Phillips Head Screwdrivers
• Lifting Equipment with Slings
• Vessel Mounting Brackets
• Required Isolation Valves
• Plumbing Components
• Personal Safety Equipment
General risk due to load.
General risk due to pressurized piping or UV Vessel.
Quartz Sleeves are fragile and potentially dangerous if broken. Handle with care.
Procedure
Important: The installation of the UV system must be carried out in accordance with local regulations and codes.
1. Install the UV system after the mechanical filtration. This eliminates debris from entering the vessel and diminishing
the unit's effectiveness, as well as potentially damaging the quartz sleeves and UV lamps.
2. Install inlet and outlet isolation valves (to be supplied by others).
3. Install UV vessel mounting brackets if required (to be supplied by others).
Note: A 46" clearance for CLP4 Series models and a 76" clearance for CLP6 Series models is required for lamp and
quartz sleeve removal.
Horizontal Installation
Horizontal installation requires the vessel outlet port to face upwards, allowing
trapped air to escape. If installed on a "by-pass filter loop" or isolated using
valves, an automatic air bleed system is required. Failure to remove trapped
air can result in rupture or heat damage to the vessel.
Vertical Installation
Vertical installation requires the bottom port to be used as the vessel's inlet and the port
closest to the electrical end to be used as the outlet; allowing trapped air to escape. If installed
on a "by-pass filter loop" or isolated using valves, an automatic air bleed system is required.
Failure to remove trapped air can result in rupture or heat damage to the vessel.
BIOSHIELD™ Commercial UV Disinfection System Installation and User's Guide
MAIN POWER
MAIN POWER
LAMP HOUR METER
LAMP HOUR METER
RESET BUTTON
RESET BUTTON
LAMP #1
LAMP #1
LAMP #4
LAMP #4
LAMP #2
LAMP #2
LAMP #5
LAMP #5
LAMP #3
LAMP #3
LAMP #6
LAMP #6