SECTION FIVE
SYSTEM SPECIFICATIONS
QUARTZ SLEEVE/
UV LAMP ACCESS
PORTS
LAMP FIELD
SAFETY COVER
C
Above: Bioshield™ UV Disinfection System polymer UV vessel, outfitted with raised flanges (available in all vessel diameters).
Electrical and Flow Specifications
Lamps/
2
Model
Watts
CLP41A6-XN
1/130
CLP42A6-XN
2/130
CLP43A6-XN
3/130
CLP43A8-XN
3/130
CLP44A8-XN
4/130
CLP45A8-XN
5/130
CLP46A10-XN
6/130
CLP47A10-XN
7/130
CLP47A12-XN
7/130
CLP48A12-XN
8/130
CLP61A6-XN
1/320
CLP62A6-XN
2/320
CLP63A6-XN
3/320
CLP63A8-XN
3/320
CLP64A8-XN
4/320
CLP65A8-XN
5/320
CLP66A10-XN
6/320
CLP67A10-XN
7/320
CLP67A12-XN
7/320
CLP68A12-XN
8/320
CLP69A14-XN
9/320
CLP610A16-XN
10/320
CLP611A18-XN
11/320
CLP612A20-XN
12/320
BIOSHIELD™ Commercial UV Disinfection System Installation and User's Guide
WATER
OUTLET
PORT
WATER DRAIN PORT
REMOVABLE HEAD SECTION
UV-C
Spectrum
Amps Max Load @
Output
120/230 VAC
Watts
40
2.1/1.0
80
3.9/2.0
120
5.8/2.9
120
5.8/2.9
160
7.5/3.7
200
9.4/4.7
240
11.2/5.6
280
13.3/6.5
280
13.3/6.5
320
15.0/7.5
98
3.2/1.6
196
6.0/3.0
294
9.0/4.5
294
9.0/4.5
392
12.0/6.0
490
15.0/7.5
588
18.0/9.0
686
11.0
686
11.0
784
13.0
882
14.0
980
16.0
1,078
17.0
1,176
19.0
A
Max. Flow Rate
Max.
PSI
150
150
150
150
150
150
120
120
90
90
150
150
150
150
150
150
120
1
120
1
90
1
90
1
50
1
50
1
50
1
50
WATER TEMP. SENSOR PORT
UV INTENSITY SENSOR PORT
B
Max. Flow Rate
@ 90% UVT
@ 90% UVT
40 mJ/cm2
60 mJ/cm2
(GPM)
(GPM)
49
90
125
167
227
272
365
430
492
555
113
200
279
372
505
606
814
953
1095
1235
1462
1690
1963
2335
WATER
INLET
PORT
33
60
83
111
151
181
244
287
328
369
75
133
186
247
336
403
542
638
729
823
974
1127
1308
1555

Hide quick links:

Advertisement

Table of Contents
loading