Insulate Refrigerant Lines; Field Wiring - Hussmann RFLNS Installation & Operation Manual

Table of Contents

Advertisement

P/N 0539221_T

INSULATE REFRIGERANT LINES

Check that all suction lines are adequately
covered with insulation from case penetration
to compressor, including suction service
valves, and accumulator on low temp units,
as some insulation may have been dislodged
duing shipping and installation. Suction
lines are insulated to prevent condensation;
extra insulation is provided to cover the field
connected tubing sections. These exposed
sections must be covered with insulation.
Check that all suction lines are adequately
covered with insulation from case penetration
to compressor; including suction service valves
as some insulation may have been dislodged
during shipping and installation. Do not
locate the tubing above the electrical box in
order to prevent condensation from dripping
onto electrical components.
Compressor

FIELD WIRING

All wiring must be in compliance with NEC
and local codes. Field wiring must be sized for
component amperes stamped on the serial plate.
Actual ampere draw may be less than specified.
Field wiring lands on the line side of the service
disconnect.
Terminal blocks are used for field connection
of the 120V single phase and 208/230V single
phase power supply. The terminal blocks
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
are located inside the electrical box on top
of the case. The wiring diagram and circuit
requirements are provided on the Technical
Data Sheets provided with the case and
condensing unit. A disconnect switch may be
provided as an option. When this switch is off,
some electrical terminals in the case wireway
may be energized. The wiring connection for
the condensing unit is provided with 5-ft leads
and
connected to the condensing unit electrical
box, and the leads are connected to the
condensing unit input terminals. The heated
condensate pan, if provided, is plugged into
the GFCI receptacle at the top of the case.
Insulation
Electrical Box
IMPORTANT:
Refer to specific wiring diagrams or condensing
unit data sheets. Field wiring lands on the line side
of the service disconnect.
1
-inch terminals. The conduit must be
4
Disconnect Switch
Reference Wiring Diagram for
Appropriate Terminal Connections.
Connectors
Terminal Strip
Control Box and Disconnect Wiring
Service Disconnect to be installed
on Case or Store Wall.
Freedom Line Reach-in
2-7
Conduit Wire