Mitsubishi MELSEC QS Series User Manual page 37

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

2
PERFORMANCE SPECIFICATION
Item
Internal relay [M]
Link relay [B]
Timer [T]
Retentive timer [ST]
Counter [C]
Data register [D]
Link register [W]
Annunciator [F]
Edge relay [V]
Link special relay [SB]
Link special register [SW]
Special relay [SM]
Special register [SD]
RUN/PAUSE contact
Timer function
Allowable instantaneous power failure
period
5VDC internal current consumption
H
External dimensions
W
D
Weight
Protection of degree
Remark
Table2.1 Performance Specifications (Continue)
6144 points by default (M0-6143) (changeable)
2048 points by default (B0 to 7FF) (changeable)
512 points by default (T0 to 511) (changeable)
(Sharing of low- and high-speed timers)
The low- and high-speed timers are specified by the instructions.
The measurement unit of the low- and high-speed timers is set up by
(Low-speed timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed timer: 0.1 to 100ms, 0.1ms unit, 10ms by default)
0 point by default (sharing of the low- and high-speed retentive timers)
The low- and high-speed retentive timers are specified by the instructions.
The measurement unit of the low- and high-speed retentive timers is set
up by parameters.
(Low-speed retentive timer: 1 to 1000ms, 1ms unit, 100ms by default)
(High-speed retentive timer: 0.1 to 100ms, 0.1ms unit, 10ms by default)
• Normal counter: 512 points by default (C0 to 511) (changeable)
6144 points by default (D0 to 6143) (changeable)
2048 points by default (W0 to 7FF) (changeable)
1024 points by default (F0 to 1023) (changeable)
1024 points by default (V0 to 1023) (changeable)
1536 points (SB0 to 5FF)
1536 points (SW0 to 5FF)
5120 points (SM0 to 5119)
5120 points (SD0 to 5119)
One contact can be set up in X0 to 17FF for each of RUN. No PAUSE
Year, month, date, hour, minute, second and day-of-week
(leap year automatically identified)
Accuracy: -3.18 to +5.25s (TYP. +2.14s) / d at 0
Accuracy: -3.18 to +2.59s (TYP. +2.07s) / d at 25
Accuracy: -12.97 to +3.63s (TYP. -3.16s) / d at 55
Varies depending on the power supply module
Refer to the following manual for the general specifications.
QSCPU User's Manual (Hardware Design, Maintenance and Inspection)
QS001CPU
parameters.
(changeable)
contact.
0.43A
98mm
55.2mm
115mm
0.29kg
IP2X
1
Remarks
2
The number of points
can be changed within
the setting range.
3
Section 9.2
4
The number of device
points is fixed.
Setting by parameters.
5
Section 6.11
----
6
----
----
----
----
----
----
7
8
2
- 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qs001cpu

Table of Contents