6
FUNCTIONS
(4) Setting the Output (Y) Status when Changing from STOP Status to RUN
(5) Precaution
6
- 44
6.10 Setting of Output (Y) Status when Changing between STOP and RUN
Status
Set the output (Y) status when changing from the STOP status to the RUN status in
the PLC system of the PLC parameter dialog box.
Output mode at
STOP to RUN
When performing forced ON at STOP status of the CPU module, the output at
switching from STOP status to RUN status is as shown in Table6.15.
Table6.15 Output at switching from STOP status to RUN status after performing forced ON to output (Y)
Output mode at switching
from STOP to RUN
Output (Y) status prior to
STOP is output
Outputs (Y) is cleared.
Diagram 6.22 PLC system screen
.
Output at switching from STOP status to RUN status
Output the status before STOP
If the output (Y) is OFF before STOP, ON status is not maintained
Maintain ON status