Functions Available By Use Of Gx Configurator-St - Mitsubishi MELESEC-ST User Manual

Table of Contents

Advertisement

9 FUNCTIONS AVAILABLE BY USE OF SOFTWARE

9.2.2 Functions Available by Use of GX Configurator-ST

Function
Information monitor function
Status monitor function
Online module change
function
Forced output test function
Input response time setting
monitoring function
Setting monitoring of output
status (CLEAR/HOLD) at
module error
Power supply capacity check
function
1) Operate with GXConfigurator-ST.
2) Execute a command from the master station to perform operation.
3) Use the button or switch of the head module to perform operation.
1: For the operation of GX Configurator-ST, refer to the GX Configurator-ST Operating Manual.
2: For details, refer to the MELSEC-ST PROFIBUS-DP Head Module User's Manual.
9 - 5
Monitors various information of the head module and slice
modules.
Monitors the operating status of the slice modules and the error
history, etc. of the head module.
Replaces an I/O module or intelligent function module while
external power supply is on.
Note that the power distribution modules cannot be replaced.
Forcibly outputs the Bw.n Bit Output, Ew.n Error Clear and
Ww.n Word Output of the head module and slice modules.
Monitors the response time setting (0.5ms/1.5ms) of the input
module.
Monitors the output status (CLEAR/HOLD) of the output
module.
CLEAR: Output is forcibly turned off when a module
becomes faulty.
HOLD: Output is held in the status as when a module
becomes faulty.
Judges whether the 5VDC maximum rated output current of the
power distribution module is sufficient for the total 5VDC internal
current consumption of the slice modules.
Description
MELSEC-ST
Operation
Reference
method
section
1) 2) 3)
1
2
2
1
This
section (1)
This
section (2)
1
: Applicable,
: N/A
9 - 5