St1Y2-Tpe3 Transistor Output Module (Source Type) - Mitsubishi MELESEC-ST User Manual

Table of Contents

Advertisement

7 I/O MODULES

7.2.4 ST1Y2-TPE3 transistor output module (source type)

Specifications
Number of occupied slice
modules
Number of occupied I/O points
Number of output points
Isolation method
Rated load voltage
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at ON
OFF to ON
Response time
ON to OFF
Surge suppressor
Protection function
Wiring method for common
Dielectric withstand voltage
Insulation resistance
Noise durability
Protection of degree
Operating status
Available base module
Available coding element
5VDC internal current
consumption
Weight
2-wire
external load
11
12
L
13
21
L
22
23
1: This FG terminal is not connected.
(Grounded at the FG contact of the base module for power distribution module.)
2: Shield is grounded via the base module for the power distribution module.
3: Connection from power distribution module.
7 - 9
Type
CC-Link: 0 point for input, 2 points for output
PROFIBUS-DP: 2 points for each of input and output
24VDC (+20/-15%, ripple ration within 5%)
0.15VDC (TYP.) 1.0A, 0.2VDC (MAX.) 1.0A
1.5ms or less (rated load, resistive load)
• Yes (thermal protection, short circuit protection)
• Indicated by LED (When protective function is activated,
ERR. LED turns on and signal is output to head module)
• Automatic recovery
500VAC for 1 minute across DC external terminals and FG
10M
or larger by insulation resistance tester across DC external
By noise simulator of 500Vp-p noise voltage, 1
First transient noise IEC61000-4-4: 1kV (bundle)
Spring clamp type
Screw clamp type
ST1A-CKY-08 (orange) (factory-fit) Refer to Chapter 8 for details.
(0.10A is shown on the rating plate of the module.)
External Connections
Base Module
1
3
Constant
24G
3
Voltage
Circuit
+24V
Y0
24G
Shield
Y1
24G
Shield
2
Transistor Output Module (source type)
ST1Y2-TPE3
1
2 points
Photocoupler
1.0A/point, 2.0A/common
2.0A, 10ms or less
0.3mA or less
0.5ms or less
Zener diode
2 points/common
terminals and FG
and 25 to 60Hz noise frequency
IP20
ON indication (LED)
ST1B-S3Y2 2-wire type + shield
ST1B-E3X2 2-wire type + shield
0.095A (TYP. all points ON)
0.03kg
Output Module
s noise width
Terminal Block
Terminal Layout
No.
11
12
13
21
11
21
22
23
12
22
13
23
Module front
view
MELSEC-ST
Appearance
ST1Y2
-TPE3
RUN
ERR.
11
21
Signal Name
Y0
24G
Shield
Y1
24G
Shield
7 - 9

Advertisement

Table of Contents
loading