11 EMC AND LOW VOLTAGE DIRECTIVE

11.1.1 EMC Directive standards

11
Specification
EN55011
Radiated emissions *
EN55011
Conducted emission
EN61000-4-2
Electrostatic immunity *
EN61000-4-3
EN61131-2 :
Radiated electromagnetic field
2003
immunity *
EN61000-4-4
Fast transient burst immunity *
EN61000-4-5
Surge immunity *
EN61000-4-6
Conducted immunity *
1: QP: Quasi-peak value, Mean : Average value
2: The MELSEC-ST series is an open type device (device incorporated in another device) and must be installed in a conductive control
panel.
The corresponding test is performed while the MELSEC-ST series is installed inside a control panel.
3: Use an external power supply introduced in Section 11.1.4. Mount the external power supply and MELSEC-ST series modules to the
same DIN rail.
Wiring connected between the following modules is treated as internal wiring and it is tested as an integrated system.
Between external SYS. power supply and bus refreshing module (ST1PSD)
Between external AUX. power supply and bus refreshing module (ST1PSD)
Between external AUX. power supply and power feeding module (ST1PDD)
11 - 2
The EMC Directive standards are listed below.
Test item
Radio emissions from the product
2
are measured.
Noise emissions from the product
to the power line is measured.
Immunity test in which static
electricity is applied to the
2
equipment.
Immunity test in which field is
irradiated to the product.
2
Immunity test in which burst noise
is applied to the power and signal
2
3
*
lines.
Immunity test in which a lightning
surges are applied to power and
3
signal lines.
Immunity test in which high-
frequency noise is applied to power
3
and signal lines.
Test details
30 to 230 MHz QP: 40 dB
(10 m in measurement range) *
230 to 1000 MHz QP: 47 dB
(10 m in measurement range)
150 to 500 kHz QP: 79 dB, Mean: 66 dB *
500 to 30 MHz QP: 73 dB, Mean: 60 dB
8 k V Aerial discharge
4 k V Contact discharge
1.4 to 2.0 GHz, 80 to 1000 MHz, 10 V/m, 80%
AM modulation @ 1 kHz
AC power line: Common mode 2 kV
I/O, analog, communication (shielded):
Common mode 1 kV
AC power line: Common mode 2 kV,
differential mode 1 kV
I/O, analog, communication (shielded):
Common mode 1 kV
0.15 to 80 MHz, 80% AM modulation @1 kHz,
3 Vrms
MELSEC-ST
Standard value
V/m
1
V/m
1
11 - 2