Output Wiring - Mitsubishi FX2N-5A User Manual

Table of Contents

Advertisement

FX2N-5A Special function block
5.3

Output Wiring

Please refer to 5.2 for the wiring for "24+", "24-" terminals.
Figure 5.3: Output Wiring
Voltage output
*1
Shielded cable
Inverter,
etc.
*3
Current output
*1
Shielded cable
Recorder,
etc.
Figure 5.4: Crimp Terminals
6.2 mm (0.24" )
or less
FX
-5A
2N
OUT
V+
I+
VI-
*2
FX
-5A
2N
OUT
V+
N.C.
I+
VI-
*2
For M3 (0.12")
*1 Use a twisted pair shielded cable for the
analog output. This cable should be wired
away from power lines or any other lines
which could induce noise.
*2 Apply 1-point grounding at the load side of
the output cable (grounding: 100Ω or less).
*3 If electrical noise or a voltage ripple exists at
the output, connect a smoothing capacitor of
0.1 to 0.47µF, 25V.
- Shorting the voltage output terminal or
connecting the current output load to the
voltage output terminal may damage the
FX
-5A.
2N
- For the terminal arrangement, refer to Section
2.
6.2 mm (0.24")
or less
Wiring 5
For M3 (0.12")
5-3