Diagnostic message
Overload or internal sensor
supply short-circuit to ground
F-address memory not
accessible
No valid F-address available
Sensor signal flutters
Frequency too high
Undertemperature
Discrepancy failure
Input shorted to P
Supply voltage too high
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Fault
Meaning
code
307
Possible causes:
H
The internal sensor supply is short-
circuited to ground.
Impermissibly high electromagnetic
interference is present.
30D
F-source address placed in the electronic
H
coding element and F-destination address
cannot be accessed.
30E
No valid PROFIsafe address is stored in the
H
retentive memory. Possible causes:
Initial commissioning
Deliberate parameter change of the
PROFIsafe address
Deviation between setpoint and actual
configuration of the plant
310
Too many signal changes have occurred
H
within the time configured with the
"Monitoring window" parameter.
The "Monitoring window" parameter
setting is too high.
The "Number of signal changes"
parameter setting is too low.
A momentary interruption/short-
circuit of the sensor cable (loose
contact) is present.
Impermissibly high electromagnetic
interference is present.
The sensor/switch is bouncing.
The sensor is defective.
311
The switching frequency of the sensor is
H
too high.
312
The minimum permissible temperature
H
limit has been violated.
314
The discrepancy time set for 1oo2
H
evaluation was exceeded.
The error message is output for channel
n+4.
Additional information: see error codes
300
... 303
.
H
H
31C
The input signal is short-circuited to L+.
H
321
The supply voltage is too high.
H
Interrupts/diagnostic messages
6.3 Diagnostic messages
Remedy
Eliminate the overload.
Eliminate the short-circuit in the
process wiring.
Check the "Sensor supply"
parameter.
Eliminate/reduce the
electromagnetic interference.
Check whether the coding element is
available. Replace the coding element,
if necessary.
Perform the assignment of the
PROFIsafe address during initial
commissioning or deliberate
parameter changes.
Check the consistency between the
setpoint and actual configuration.
Check the "Monitoring window"
parameter.
Check the "Number of signal
changes" parameter.
Check the process wiring.
Eliminate/reduce the
electromagnetic interference.
Replace the sensor.
Reduce the switching frequency of the
sensor.
Operate the F-module within the
specified temperature range. (See
Technical specifications (Page 65))
Additional information: see error codes
300
... 303
.
H
H
Eliminate the short-circuit.
Check the supply voltage.