Siemens SIMATIC ET200SP Function Manual

Siemens SIMATIC ET200SP Function Manual

Hide thumbs Also See for SIMATIC ET200SP:

Advertisement

Quick Links

SIMATIC
ET200SP
Safety engineering
with AS‑Interface in the
SIMATIC ET 200SP, including
typical circuit diagram
Function Manual
08/2020
A5E44991382002A/RS-AB/002
Legal information
About this documentation
Introduction
Circuit diagram example
Commissioning and
operation
Appendix
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET200SP

  • Page 1 Legal information About this documentation SIMATIC Introduction Circuit diagram example ET200SP Safety engineering Commissioning and with AS‑Interface in the operation SIMATIC ET 200SP, including typical circuit diagram Appendix Function Manual 08/2020 A5E44991382002A/RS-AB/002...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Legal information ..........................5 Legal information ........................ 5 About this documentation ........................7 Additional documentation ....................7 Purpose of the documentation ..................... 7 Target group ........................7 Required knowledge ......................7 Introduction ............................9 AS-Interface ......................... 9 3.1.1 AS-Interface basics .......................
  • Page 4 Table of contents Commissioning and operation ......................51 Commissioning ........................51 5.1.1 Preparation ........................51 5.1.2 Load S7 project into the CPU ....................51 5.1.3 Assigning PROFIsafe addresses ................... 52 Using the application ......................53 Evaluating the safety function .................... 54 Appendix .............................
  • Page 5: Legal Information

    Siemens AG and/or a subsidiary company of Siemens AG ("Siemens"). They are not binding and do not claim to be complete or functional with regard to configuration or equipment. The application examples do not represent customer- specific solutions, but rather, only provide help for typical tasks.
  • Page 6 1.1 Legal information Additional notes: Siemens reserves the right to make changes to these application examples at any time without prior notice. In cases of discrepancies between the suggestions in the application examples and other Siemens publications, such as catalogs, then the content of the other documentation shall have precedence.
  • Page 7: About This Documentation

    Safety, and uses a typical circuit diagram to show how safety functions can be implemented with AS-i in the ET 200SP distributed I/O system. Further information on the topic of AS-i can be found in the AS-i System Manual (https://support.automation.siemens.com/WW/view/de/51579885) and on the Internet (https://www.siemens.com/as-interface). Target group This documentation contains information for the following target groups: •...
  • Page 8 About this documentation 2.4 Required knowledge Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 9: Introduction

    The safe AS-i signals are transmitted directly to a safe PLC, where they can be further processed. Siemens AS-i masters and Siemens AS-i modules are integrated in SIMATIC STEP 7, and can be inserted into the configuration at the click of a mouse.
  • Page 10: Network Structure

    Introduction 3.1 AS-Interface 3.1.2 Network structure Linear, star, and tree topologies are supported by the AS-Interface, making assembly practical with hardly any restrictions. Linear structure Nodes All devices are connected to a continuous cable. Star structure Nodes The nodes are connected to one another in a star-shaped structure. Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 11 Introduction 3.1 AS-Interface Tree topology Nodes The tree topology is similar to the star topology, but with any number of branches. Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 12: Creating An As-Interface Network

    Introduction 3.1 AS-Interface 3.1.3 Creating an AS-Interface network An AS-i network always comprises a master, an AS-i power supply unit, and the AS-i slaves. AS-i is a single master system, i.e. a master module collects the data from multiple AS-i slaves and transfers it to the process image of the PLC.
  • Page 13: Number Of Nodes

    Introduction 3.1 AS-Interface 3.1.4 Number of nodes An AS-i network contains a maximum of 62 slaves with unique AS-i addresses. The AS-i master can manage 31 different addresses for the data exchange, whereby it can subdivide and reference each address as an A address or B address. Slaves with standard addressing can be set to an address in the range 1 ...
  • Page 14: Network Extension

    Introduction 3.1 AS-Interface 3.1.5 Network extension Figure 3-2 Network extension – previously a maximum of 100 m per segment An AS-i line can be up to 100 m long without additional components. Repeaters can be used to increase the maximum possible cable length. Two repeaters can be connected in series, which can extend the network to 300 m as a linear structure.
  • Page 15: As-I Safety

    (F-CPU). This system is not covered in this documentation. Further information can be found on the Internet (http://www.siemens.de/sirius-mss). AS-i Safety is also referred to as ASIsafe. Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram...
  • Page 16: As-I Safety Product Overview

    Introduction 3.2 AS-i Safety product overview AS-i Safety product overview This section provides an overview of ASIsafe components as well as the accessories available to help you assemble, install, and use these components. The tables contain images of the products and their features. AS-i safety components Product Features...
  • Page 17 Introduction 3.2 AS-i Safety product overview Safe modules Easy integration of safe signals, both in the control cabinet and in the field • IP65 / IP67 or IP20 degree of protection • Compact dimensions from a width of 17.5 mm •...
  • Page 18 Introduction 3.2 AS-i Safety product overview System components and accessories Function / product Properties Power supply units and data decoupling The AS-i power supply unit allows the simultaneous transmission of data and power on the same two-wire line. Alternatively, a combination of a standard power supply unit and AS-i data decoupling can be used.
  • Page 19 Introduction 3.2 AS-i Safety product overview Range extension Lower infrastructure costs, more possibilities of use and greater freedom for plant planning Extension plug Repeater • Extension of an AS-i segment to a max. of 200 m with extension plug (without additional power supply unit) •...
  • Page 20 Introduction 3.2 AS-i Safety product overview Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 21: Circuit Diagram Example

    Circuit diagram example Knowledge required The following application example shows how conventional safety functions, such as emergency stop shutdown and protective door monitoring in the ET 200SP system can be configured and programmed with AS-Interface via the TIA Portal. Knowledge required The following knowledge and skills are required: •...
  • Page 22 Circuit diagram example 4.2 Operating principle Figure 4-1 Circuit diagram example Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 23 SIL 2 or PL d. Further information is contained in the PDF under the following link "concerning the use of safety switches up to SIL 2 or PL d (http://support.automation.siemens.com/WW/view/de/35443942)". Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram...
  • Page 24: Emergency Stop

    Circuit diagram example 4.2 Operating principle 4.2.2 Emergency stop The emergency stop command device is a component that is widely used to protect people, equipment and the environment against possible hazards, and to initiate stopping in an emergency. Equipment, functional aspects and design guidelines for emergency stop are listed in EN ISO 13850.
  • Page 25: Monitoring The Position Of The Protective Door And Tumbler Function

    Circuit diagram example 4.2 Operating principle 4.2.3 Monitoring the position of the protective door and tumbler function The position of the protective door is monitored by a SIRIUS 3SF1 position switch. The position switch detects the position of the protective door by a separate actuator. This moves into the position switch when the protective door closes.
  • Page 26 Circuit diagram example 4.2 Operating principle There are basically three different combinations for forwarding the contacts of the AS-i position switch with tumbler as ASIsafe channel 1 and 2 to the controller for evaluation: 3SF13 version ASIsafe channel 1 ASIsafe channel 2 3SF13 ...
  • Page 27: Control And Monitoring Of The Actuator

    Circuit diagram example 4.2 Operating principle For this reason, a 1BA4 version of the 3SF1 position switch is used in the application example described here. See the figure below: • 1st normally closed contact of actuator (state: door closed): 11 / 12 •...
  • Page 28: Hardware And Software Components

    Circuit diagram example 4.3 Hardware and software components Hardware and software components 4.3.1 Validity This application example is valid for: • All SIMATIC F controllers • STEP 7 Professional as from V 15 4.3.2 Components used The application was created with the following components. Hardware components Component Quantity Article No.
  • Page 29: Example Of Wiring

    4.3 Hardware and software components 4.3.3 Example of wiring The wiring example is available for download in the Internet (http://support.automation.siemens.com/WW/view/en/109769506) as a PDF and EPLAN macro. 4.3.4 Sample data and projects The following table contains all the files and projects used in this example.
  • Page 30: Tia Portal Configuration

    A detailed guide to configuring CM AS-i Master ST is available in the "Configuration" Section of the "AS-Interface Master CM AS-i Master ST (https://support.industry.siemens.com/cs/ww/view/71756485)" Manual. Configuration of the F-CM Safety ST A detailed guide to configuring the F-CM Safety ST is available in the "Configuration" Section of the "ET 200SP Failsafe Module F-CM AS-i Safety ST...
  • Page 31: Configuring Et 200Sp System

    Circuit diagram example 4.4 TIA Portal configuration 4.4.3 Configuring ET 200SP System In this example, an ET 200SP F-CPU is configured with TIA Portal V15.1. In other versions, the representation may be slightly different; it then applies analogously. The steps shown apply correspondingly if an ET 200SP station is used with an interface module (e.g.
  • Page 32 Circuit diagram example 4.4 TIA Portal configuration Result: Figure 4-4 Adding the two AS-i modules to the ET 200SP station Figure 4-5 Creating a new AS-i network Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 33 Circuit diagram example 4.4 TIA Portal configuration 9. Insert the F-DQ 4x24VDC/2A PM HF module on the right of the F-CM module, and activate its 1st channel in its "DQ parameters". 10. Insert the DI 8x24VDC HF module and a server module on the right of the F-DQ module. Figure 4-6 Complete configuration of the ET 200SP station Note...
  • Page 34: Adding As-I Slaves

    Circuit diagram example 4.4 TIA Portal configuration 4.4.4 Adding AS-i slaves Configure an AS-i slave in the AS-i subnet. In the following example, an emergency stop command device is connected to an ASIsafe F adapter. Other AS-i (ASIsafe) slaves can be correspondingly configured. Procedure: 1.
  • Page 35 Circuit diagram example 4.4 TIA Portal configuration Tip: Display the AS-i addresses on the slaves by activating the "Show addresses" function (symbol with eye in the menu bar of the network view, above the empty area). Figure 4-9 Display addresses Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 36: Setting F Parameters

    F-CPU. The individual parameters are explained briefly below. Further information may be found in the "SIMATIC Safety - Configuring and Programming (https://support.automation.siemens.com/WW/view/de/54110126)" Manual. Figure 4-10 Parameters of the F-CM AS-i Safety ST The F monitoring time [ms] is the PROFIsafe monitoring time for the safety-related communication between F-CPU and F I/O.
  • Page 37: Configuring Safe As-I Slave Monitoring

    Circuit diagram example 4.4 TIA Portal configuration 4.4.6 Configuring safe AS-i slave monitoring To change the safe I/O addresses and AS-i slave parameters, open the Properties dialog box of the F-CM AS-i Safety ST in the device view of the ET 200SP station. Under the "Safe inputs"...
  • Page 38 Circuit diagram example 4.4 TIA Portal configuration In the 1oo2 evaluation, equivalent both inputs of the safe AS-i slave are occupied, either by a 2-channel encoder or by two single-channel encoders. The two single-channel sensors then belong together functionally as a pair, e.g. two position switches of one door monitoring. The input signals are compared internally for equivalence.
  • Page 39 Circuit diagram example 4.4 TIA Portal configuration The safe monitoring of the position switch is then configured as follows. The explanation of the individual parameters can be found in Section 4.4.5 (Page 36). A 1oo1 evaluation is selected to monitor the position switch because the switch used (version 3SF13 ... 1BA4) is already monitored for discrepancy (see Section 4.2.3 (Page 25)).
  • Page 40 Circuit diagram example 4.4 TIA Portal configuration The solenoid for releasing the door tumbler is controlled via a standard output of the AS-i slave installed in the position switch (output bit 0, see "Digital I/O"; Q0.0 in this example). The read back signal (normally closed contact) of the solenoid is the second fail-safe channel of the AS-i slave (see Section 4.2.3 (Page 25), 1BA4 version).
  • Page 41 Circuit diagram example 4.4 TIA Portal configuration Finally, the F-DQ module is configured to control the redundant contactors. Here again, the F parameters remain unchanged (default setting). The setting of the safe monitoring can be taken from the following figure. Figure 4-16 Configuration of the F-DQ module Note...
  • Page 42: Minimum Number Of Slaves For As-I Safety Applications

    Circuit diagram example 4.4 TIA Portal configuration 4.4.7 Minimum number of slaves for AS-i Safety applications In a normal application, an AS-i network contains more than 5 AS-i slaves. However, only 3 AS-i slaves are used for this example. In this case, the specifications in EN 60262-2 (AS-i specification) for the minimum cycle time and minimum number of slaves for AS-i Safety applications must be observed.
  • Page 43 Circuit diagram example 4.4 TIA Portal configuration Figure 4-17 Hardware configuration with virtual slaves Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 44: Assigning Fail-Safe Addresses To Et 200Sp

    Circuit diagram example 4.4 TIA Portal configuration 4.4.8 Assigning fail-safe addresses to ET 200SP After setting the F parameters of the F-CM AS-i Safety ST module, the PROFIsafe-/F destination address still has to be assigned to the extended module (real hardware). Fail-safe ET 200SP modules do not have DIP switches with which you can assign the unique F destination address (= PROFIsafe address) to each module.
  • Page 45: Teaching Asisafe Code Sequences

    Circuit diagram example 4.4 TIA Portal configuration 4.4.9 Teaching ASIsafe code sequences To perform safety-related communication, each safe AS-i input slave sends a code sequence over the AS-i bus. To prevent a mix-up of AS-i input slaves on the AS-i bus, each AS-i input slave sends a different code sequence.
  • Page 46 Further information on the topic of code sequences can be found in the "T 200SP fail-safe module F-CM AS-i Safety ST (https://support.industry.siemens.com/cs/ww/de/view/90265988)" Manual in the "Code sequences" section. Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram...
  • Page 47: Tia Portal Programming

    Circuit diagram example 4.5 TIA Portal programming TIA Portal programming In this typical circuit diagram, the focus is on the safety-related switching of the machine. Therefore, operational switching is not taken into account, and no standard user program is programmed. In this example, the user must implement the operational switching – adapted to the conditions of the machine –...
  • Page 48 Data exchange between standard user program and safety program In the event of inadequate programming, data corruption resulting in a CPU/ system stop may occur in the communication between standard user program and safety program (see (https://support.industry.siemens.com/cs/document/19183712/what-should-you-do-if-the-f- cpu-goes-into-stop-mode-and-the-message-data-corruption-in-the-safety-program-appears- in-the-diagnostics-buffer-?dti=0&lc=en-WW)). Therefore two global data blocks should be used to exchange data between the standard user program and the safety program.
  • Page 49 Further information on the data exchange between standard user program and safety program can be found in the "SIMATIC Safety - Configuring and Programming" Manual. (https://support.industry.siemens.com/cs/ww/en/view/54110126) Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 50 Circuit diagram example 4.5 TIA Portal programming Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...
  • Page 51: Commissioning And Operation

    Preparation 1. Download the "E-Stop_SIL3_Protective_door_tumbler_SIL2_AS-i.zap15_1" project file. Link: . (http://support.automation.siemens.com/WW/view/en/109769506) 2. Save the file in any folder on your computer. 3. Set the IP address of the PG/PC so that the PG/PC is in the same subnet as the CPU.
  • Page 52: Assigning Profisafe Addresses

    Commissioning and operation 5.1 Commissioning 5.1.3 Assigning PROFIsafe addresses For safe communication between the F-CPU and the fail-safe modules (F-CM AS-i Safety and F-DQ), the correct PROFIsafe addresses must be assigned to the modules. To do this, follow the steps in Section 4.4.8. (Page 44) Note Since the PROFIsafe address is stored in the electronic coding element of the ET 200SP slot, this step is only necessary if a PROFIsafe address is missing, or if a different one was assigned.
  • Page 53: Using The Application

    Commissioning and operation 5.2 Using the application Using the application Starting a machine Action Note Close the protective door. Move the toggle switch into the position that The voltage in the solenoid is switched off and the locking locks the protective door. mechanism moves into the actuator.
  • Page 54: Evaluating The Safety Function

    An evaluation is made according to both EN ISO 13849-1 and EN 62061 with the Safety Evaluation Tool (SET) (http://siemens.de/safety-evaluation-tool). The result of the evaluation - the SET file (http://support.automation.siemens.com/WW/view/en/109769506)- is added to the SIOS entry of this document. Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram...
  • Page 55: Appendix

    (https://support.industry.siemens.com). Technical Support The Technical Support of Siemens Industry provides you with fast and competent support regarding all technical queries with a variety of customized portfolio elements – from basic support to customized support contracts.
  • Page 56 You can find detailed information on our range of services in the Service Catalog (https://support.industry.siemens.com/cs/sc). Industry Online Support app You will receive optimum support wherever you are with the "Siemens Industry Online Support" (https://support.industry.siemens.com/cs/ww/de/sc/2067) app. The app is available for Apple iOS, Android and Windows Phone.
  • Page 57: Links And Literature

    Appendix 6.2 Links and literature Links and literature Topic Siemens Industry Online Support (https://support.industry.siemens.com) Link (http://support.automation.siemens.com/WW/view/en/109769506) to the entry page of the application example Project file (http://support.automation.siemens.com/WW/view/en/109769506) Version history Version Date Change V1.0 09/2019 First edition V2.0 08/2020 Correction: Non-safety-related tumbler via integrated standard output of 3SF1324-1S.21-1BA4...
  • Page 58 Appendix 6.3 Version history Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram Function Manual, 08/2020, A5E44991382002A/RS-AB/002...

Table of Contents