Siemens SIMATIC ET 200SP Equipment Manual page 20

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.1 Parameters
Parameters
F-I/O DB name
DI parameters:
Sensor supply
Sensor supply n
Short-circuit test
Time for short-circuit test
Startup time of sensor after
short-circuit test
Channel parameters
Channel n, n+4
Sensor evaluation
Discrepancy behavior
Discrepancy time
Reintegration after
discrepancy error
Channel n
Activated
Channel failure acknowledge •
Sensor supply
22
Value range
Is proposed by the F-
system
Enable
Disable
Enable
0.5 ms to 2 s
4.2 ms
0.5 ms to 2 s
4.2 ms
1oo2 evaluation,
1oo1 evaluation
equivalent
1oo2 evaluation,
equivalent
1oo2 evaluation,
non-equivalent
Supply value 0
Supply value 0
Supply last valid
value
5 ms to 30 s
5 ms
Test 0-Signal not
Test 0-Signal not
necessary
necessary
Test 0-Signal
necessary
Enable
Enable
Disable
(S7-300/400)
Manually
Parameter is not
Automatically
supported (S7-
1200/1500) Manual
The value range
offered depends on the
F-CPU used and the
parameter assignment
of the F-parameter
"Reintegration after
channel fault".
Sensor supply n
Sensor supply 0 to
7
External sensor
supply
Default
Parameter
reassignment in
RUN
No
No
No
No
No
No
No
No
No
No
No
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Scope
Module
Channel
Channel
Channel
Channel pair
Channel pair
Channel pair
Channel pair
Channel
Channel
Channel

Advertisement

Table of Contents
loading

Table of Contents