Interrupts/diagnostic messages
6.3 Diagnostic messages
Diagnostic message
Diagnostic queue overflow
Discrepancy failure, channel
status 0/0
Discrepancy failure, channel
status 0/1
Discrepancy failure, channel
status 1/0
Discrepancy failure, channel
status 1/1
Input signal not recorded
unique
Internal sensor supply short-
circuit to P
60
Fault
Meaning
code
13E
Overflow of the diagnostic memory. Not
H
all pending diagnostics could be sent.
This error can result in deactivation of the
module up to switching on/off of the
power supply.
300
The discrepancy time set for 1oo2
H
evaluation was exceeded.
Possible causes:
301
H
The process signal is faulty.
302
H
The sensor is defective.
The configured discrepancy time is too
303
H
low.
There is a short-circuit between an
unconnected sensor cable and the
sensor supply cable.
Wire break in connected sensor cable
or the sensor supply cable
An error occurred during the
discrepancy check.
305
An error has occurred during the
H
plausibility check of the input signal
between the processors.
Possible causes:
The input signal is faulty. For example,
through an impermissibly high
electromagnetic interference.
There is a high-frequency input signal.
For example, through reciprocal
interference of the sensors, or the
signal lies above the sampling
frequency of the input signal.
A momentary interruption/short-
circuit of the sensor cable (loose
contact) is present.
The sensor/switch bounces.
306
Possible causes:
H
There is a short-circuit of the internal
sensor supply with L+.
There is a short-circuit of two sensor
supplies.
The capacitance of the connected
sensor for the configured test time is
too high.
The sensor is defective.
Eliminate the previously reported error.
Check the process signal.
Replace the sensor.
Check the parameter assignment of
the discrepancy time.
Check the process wiring.
You must eliminate the occurred error
within 100 hours if no short-circuit test
has been configured for the
corresponding sensor supply.
Use shielded cables to reduce the
EMC effects.
Reduce the input frequency.
Check the wiring of the sensor.
Eliminate the short-circuit in the
process wiring.
Check the configured test time and
the process wiring.
Replace the sensor.
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Remedy