Diagnostic Messages - Siemens SIMATIC ET 200SP Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interrupts/diagnostic messages

6.3 Diagnostic messages

6.3
Diagnostic messages
Diagnostic messages
Module faults are indicated as diagnostics (module status).
Once the fault is eliminated, the F-module must be reintegrated in the safety program. For
additional information on passivation and reintegration of F-I/O, refer to the SIMATIC Safety –
Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/54110126) manual.
Table 6- 5
Diagnostics messages of the F-DI 8x24VDC HF
Diagnostic message
Overtemperature
Parameter error
Supply voltage missing
Communication fault
Mismatch of safety
destination address
(F_Dest_Add)
Safety destination address
not valid (F_Dest_Add)
Safety source address not
valid (F_Source_Add)
Safety watchdog time value is
0 ms (F_WD_Time)
Parameter F_SIL exceeds SIL
from specific device
application
58
Fault
Meaning
code
5
An excessively high temperature was
H
measured in the F-module.
10
Parameter assignment errors include:
H
The F-module cannot use the
parameters (unknown, invalid
combination, etc.).
The F-module parameters have not
been configured.
11
Missing or insufficient supply voltage L+
H
13
Possible causes:
H
An impermissibly high
electromagnetic interference is
present.
The F-module has detected an internal
error and reacted to it in a safety-
oriented manner.
40
The PROFIsafe driver has detected a
H
different F-destination address.
41
The PROFIsafe driver has detected an
H
invalid F-destination address.
42
The PROFIsafe driver has detected an
H
invalid F-source address.
43
The PROFIsafe driver has detected an
H
invalid watchdog time.
44
The PROFIsafe driver has detected a
H
discrepancy between the SIL setting of
the communication and the application.
Operate the F-module within the
specified temperature range. (See
Technical specifications (Page 65))
Once the fault has been eliminated,
the F-module must be removed and
inserted or the power switched OFF
and ON
Correct the parameter assignment.
Check whether a coding element is
available.
Check supply voltage L+ on the
BaseUnit
Check BaseUnit type
Correct the fault. The module must
then be pulled and plugged, or the
power switched OFF and ON.
If the F-module cannot be put into
operation anymore, consider a
replacement.
Check the parameter assignment of the
PROFIsafe driver and the address
setting of the F-module.
Check the parameter assignment of the
PROFIsafe driver.
Digital input module F-DI 8x24VDC HF (6ES7136-6BA01-0CA0)
Equipment Manual, 10/2021, A5E50578307-AA
Remedy